Sökning: id:"swepub:oai:DiVA.org:kth-117335" >
The comparison and ...
The comparison and analysis for loss of excitation protection schemes in generator protection
-
Shi, Z. P. (författare)
-
Wang, J. P. (författare)
-
Gajic, Z. (författare)
-
visa fler...
-
Sao, C. (författare)
-
- Ghandhari, Mehrdad (författare)
- KTH,Elektriska energisystem
-
visa färre...
-
(creator_code:org_t)
- IET, 2012
- 2012
- Engelska.
-
Ingår i: Developments in Power Systems Protection, 2012. DPSP 2012. 11th International Conference on. - : IET. - 9781849196208 ; , s. 1-6
- Relaterad länk:
-
https://urn.kb.se/re...
-
visa fler...
-
https://doi.org/10.1...
-
visa färre...
Abstract
Ämnesord
Stäng
- Loss-Of-Excitation (LOE) condition of a generator may cause severe damages on both generator and the interconnected systems. This paper analyses the behaviours of different LOE protection schemes, such as R-X, G-B, P-Q and U-I schemes, for a hydro generator, which is connected to an infinite bus. Based on the simulation results, the reliability and stability of existing LOE protection schemes are compared and a preferred scheme is selected. An improvement to the scheme is also proposed to prevent the LOE relay incorrect operation during external faults, such as short-circuit faults on busbar or transmission lines.
Ämnesord
- TEKNIK OCH TEKNOLOGIER -- Elektroteknik och elektronik (hsv//swe)
- ENGINEERING AND TECHNOLOGY -- Electrical Engineering, Electronic Engineering, Information Engineering (hsv//eng)
Nyckelord
- comparison and solutions
- Generator Protection
- Loss of excitation protection schemes
Publikations- och innehållstyp
- ref (ämneskategori)
- kon (ämneskategori)
Hitta via bibliotek
Till lärosätets databas