- This paper proposes a method to investigate the socioeconomical aspects of transformer overloading during a cold load pickup (CLPU) in residential areas. The method uses customer damage functions to estimate the cost for their power interruption and a deterioration model to estimate the cost for transformer wear due to the CLPU. A thermodynamic model is implemented to estimate the peak and the duration of cold residential load. A stochastic differential equation is used to capture the volatility of the load and to estimate the probability for transformer overloading. In a numerical example, an optimal cold load pickup for a two-area system is demonstrated where transformer overloading is allowed. In this example, an ambient temperature threshold is identified, where transformer overloading is socioeconomically beneficial.
Ämnesord
- TEKNIK OCH TEKNOLOGIER -- Elektroteknik och elektronik (hsv//swe)
- ENGINEERING AND TECHNOLOGY -- Electrical Engineering, Electronic Engineering, Information Engineering (hsv//eng)
Nyckelord
- Cold load pickup (CLPU)
- restoration
- transformer aging
- transformer loading