SwePub
Sök i LIBRIS databas

  Utökad sökning

id:"swepub:oai:DiVA.org:kth-183080"
 

Sökning: id:"swepub:oai:DiVA.org:kth-183080" > Dynamic Line Rating...

Dynamic Line Rating for Wind Power

Talpur, Saifal (författare)
Bahria University Karachi, Pakistan
Wallnerström, Carl-Johan (författare)
KTH,Elektroteknisk teori och konstruktion
Flood, Christer (författare)
Fortum Distribution AB, Sweden
visa fler...
Hilber, Patrik (författare)
KTH,Elektroteknisk teori och konstruktion
visa färre...
 (creator_code:org_t)
American Institute of Physics (AIP), 2016
2016
Engelska.
Ingår i: Journal of Renewable and Sustainable Energy. - : American Institute of Physics (AIP). - 1941-7012. ; 8
  • Tidskriftsartikel (refereegranskat)
Abstract Ämnesord
Stäng  
  • Dynamic line rating is a novel technique used to determine the actual value of available power transmission capacity of overhead lines being underestimated by static line rating. Contrary to static line rating method, this approach provides huge technical and economic benefits of transmitting the electrical energy under controlled constraints. Nevertheless, it is of utmost importance to have an accurate knowledge of dynamic ampacity before being practically implemented. Owing to dynamic line rating technique, an overhead conductor is rated on the basis of real-time ampacity. Furthermore, the real time ampacity contributes in combating the growing power transmission demand being observed over highly congested power transmission network. Contrary to dynamic line rating approach, building new overhead lines is a lengthy, expensive, and less reliable option. Another important advantage offered by the dynamic line rating approach is to allow excessive renewable power generation in the electricity network, particularly the wind power due to its correlation with real-time ampacity. Besides, dynamic ampacity and wind power integration, the paper also deals with risk analysis associated with conductor overloading. The risk involves increase in conductor sag as it transmits the power beyond its nominal capacity at a certain temperature. However, in this paper, the dynamic as well as the static ampacity of “VL3” overhead conductor is calculated on the basis of its nominal temperature (50 °C) to avoid the risk of its possible expansion and ultimately the deterioration. In addition to technical analysis, the economic analysis of integrating a 60 MW wind park with Fortum's 130 kV regional grid and of applying dynamic line rating approach on a periodically overloaded “VL3” overhead conductor is thoroughly investigated in this research work; to further know how beneficial it is to temporarily postpone the rebuilding and/or construction of a new overhead line in parallel to the existing overhead conductor (VL3).

Ämnesord

TEKNIK OCH TEKNOLOGIER  -- Elektroteknik och elektronik -- Annan elektroteknik och elektronik (hsv//swe)
ENGINEERING AND TECHNOLOGY  -- Electrical Engineering, Electronic Engineering, Information Engineering -- Other Electrical Engineering, Electronic Engineering, Information Engineering (hsv//eng)

Nyckelord

Electrical Engineering
Elektro- och systemteknik

Publikations- och innehållstyp

ref (ämneskategori)
art (ämneskategori)
kfu (ämneskategori)

Hitta via bibliotek

Till lärosätets databas

Sök utanför SwePub

Kungliga biblioteket hanterar dina personuppgifter i enlighet med EU:s dataskyddsförordning (2018), GDPR. Läs mer om hur det funkar här.
Så här hanterar KB dina uppgifter vid användning av denna tjänst.

 
pil uppåt Stäng

Kopiera och spara länken för att återkomma till aktuell vy