Temperature-controlled airflow ventilation in operating rooms compared with laminar airflow and turbulent mixed airflow

Alsved, M. (författare)
Lund University,Lunds universitet,Ergonomi och aerosolteknologi,Institutionen för designvetenskaper,Institutioner vid LTH,Lunds Tekniska Högskola,Ergonomics and Aerosol Technology,Department of Design Sciences,Departments at LTH,Faculty of Engineering, LTH
Civilis, A. (författare)
Ekolind, P. (författare)
Avidicare AB
visa fler...
Tammelin, A. (författare)
Karolinska Institute,Karolinska Institutet
Erichsen Andersson, Annette, 1966 (författare)
Gothenburg University,Göteborgs universitet,Institutionen för vårdvetenskap och hälsa,Institute of Health and Care Sciences
Jakobsson, J. (författare)
Lund University,Lunds universitet,Ergonomi och aerosolteknologi,Institutionen för designvetenskaper,Institutioner vid LTH,Lunds Tekniska Högskola,Ergonomics and Aerosol Technology,Department of Design Sciences,Departments at LTH,Faculty of Engineering, LTH,NanoLund: Centre for Nanoscience,Annan verksamhet, LTH,Other operations, LTH,Faculty of Engineering, LTH
Svensson, T. (författare)
Lund University
Ramstorp, M. (författare)
Lund University,Lunds universitet,Ergonomi och aerosolteknologi,Institutionen för designvetenskaper,Institutioner vid LTH,Lunds Tekniska Högskola,Ergonomics and Aerosol Technology,Department of Design Sciences,Departments at LTH,Faculty of Engineering, LTH
Sadrizadeh, Sasan (författare)
KTH,Strömnings- och klimatteknik,Lawrence Berkeley Natl Lab, Berkeley, CA USA,Lawrence Berkeley National Laboratory
Larsson, P. A. (författare)
Lund University,Lunds universitet,Kliniska Vetenskaper, Helsingborg,Sektion II,Institutionen för kliniska vetenskaper, Lund,Medicinska fakulteten,Clinical Sciences, Helsingborg,Section II,Department of Clinical Sciences, Lund,Faculty of Medicine
Bohgard, M. (författare)
Lund University,Lunds universitet,Ergonomi och aerosolteknologi,Institutionen för designvetenskaper,Institutioner vid LTH,Lunds Tekniska Högskola,Ergonomics and Aerosol Technology,Department of Design Sciences,Departments at LTH,Faculty of Engineering, LTH
Santl-Temkiv, T. (författare)
Aarhus University
Londahl, J. (författare)
visa färre...
 (creator_code:org_t)
W B SAUNDERS CO LTD, 2018
2018
Engelska.
Ingår i: Journal of Hospital Infection. - : W B SAUNDERS CO LTD. - 0195-6701 .- 1532-2939. ; 98:2, s. 181-190
  • Tidskriftsartikel (refereegranskat)
Abstract Ämnesord
Stäng  
  • Aim: To evaluate three types of ventilation systems for operating rooms with respect to air cleanliness [in colony-forming units (cfu/m(3))], energy consumption and comfort of working environment (noise and draught) as reported by surgical team members. Methods: Two commonly used ventilation systems, vertical laminar airflow (LAF) and turbulent mixed airflow (TMA), were compared with a newly developed ventilation technique, temperature-controlled airflow (T(c)AF). The cfu concentrations were measured at three locations in an operating room during 45 orthopaedic procedures: close to the wound (<40 cm), at the instrument table and peripherally in the room. The operating team evaluated the comfort of the working environment by answering a questionnaire. Findings: LAF and T(c)AF, but not TMA, resulted in less than 10 cfu/m(3) at all measurement locations in the room during surgery. Median values of cfu/m(3) close to the wound (250 samples) were 0 for LAF, 1 for T(c)AF and 10 for TMA. Peripherally in the room, the cfu concentrations were lowest for T(c)AF. The cfu concentrations did not scale proportionally with airflow rates. Compared with LAF, the power consumption of T(c)AF was 28% lower and there was significantly less disturbance from noise and draught. Conclusion: T(c)AF and LAF remove bacteria more efficiently from the air than TMA, especially close to the wound and at the instrument table. Like LAF, the new T(c)AF ventilation system maintained very low levels of cfu in the air, but T(c)AF used substantially less energy and provided a more comfortable working environment than LAF. This enables energy savings with preserved air quality.

Ämnesord

NATURVETENSKAP  -- Geovetenskap och miljövetenskap (hsv//swe)
NATURAL SCIENCES  -- Earth and Related Environmental Sciences (hsv//eng)
TEKNIK OCH TEKNOLOGIER  -- Medicinteknik -- Medicinsk ergonomi (hsv//swe)
ENGINEERING AND TECHNOLOGY  -- Medical Engineering -- Medical Ergonomics (hsv//eng)
MEDICIN OCH HÄLSOVETENSKAP  -- Hälsovetenskap (hsv//swe)
MEDICAL AND HEALTH SCIENCES  -- Health Sciences (hsv//eng)
MEDICIN OCH HÄLSOVETENSKAP  -- Annan medicin och hälsovetenskap (hsv//swe)
MEDICAL AND HEALTH SCIENCES  -- Other Medical and Health Sciences (hsv//eng)

Nyckelord

Surgical site infection
BioTrak
Fluorescence
Energy efficiency
Temperature-controlled
ventilation
Air sampling
Air sampling
BioTrak
Energy efficiency
Fluorescence
Surgical site infection
Temperature-controlled ventilation

Publikations- och innehållstyp

ref (ämneskategori)
art (ämneskategori)

Hitta via bibliotek

Till lärosätets databas

Kungliga biblioteket hanterar dina personuppgifter i enlighet med EU:s dataskyddsförordning (2018), GDPR. Läs mer om hur det funkar här.
Så här hanterar KB dina uppgifter vid användning av denna tjänst.

 
pil uppåt Stäng

Kopiera och spara länken för att återkomma till aktuell vy