Reliability Evaluation of Power Cables Considering the Restoration Characteristic

Mashad Nemati, Hassan, 1982- (författare)
Högskolan i Halmstad,CAISR Centrum för tillämpade intelligenta system (IS-lab)
Pinheiro Sant'Anna, Anita, 1983- (författare)
Högskolan i Halmstad,CAISR Centrum för tillämpade intelligenta system (IS-lab)
Nowaczyk, Sławomir, 1978- (författare)
Högskolan i Halmstad,CAISR Centrum för tillämpade intelligenta system (IS-lab)
visa fler...
Jürgensen, Jan Henning, 1987- (författare)
KTH,Elektroteknisk teori och konstruktion,Elkraftteknik,QED Asset Management Group,KTH Royal Institute of Technology, Stockholm, Sweden
Hilber, Patrik, 1975- (författare)
KTH,Elektroteknisk teori och konstruktion,QED Asset Management Group,KTH Royal Institute of Technology, Stockholm, Sweden
visa färre...
 (creator_code:org_t)
London : Elsevier, 2019
2019
Engelska.
Ingår i: International Journal of Electrical Power & Energy Systems. - London : Elsevier. - 0142-0615 .- 1879-3517. ; 105, s. 622-631
  • Tidskriftsartikel (refereegranskat)
Abstract Ämnesord
Stäng  
  • In this paper Weibull parametric proportional hazard model (PHM) is used to estimate the failure rate of every individual cable based on its age and a set of explanatory factors. The required information for the proposed method is obtained by exploiting available historical cable inventory and failure data. This data-driven method does not require any additional measurements on the cables, and allows the cables to be ranked for maintenance prioritization and repair actions.Furthermore, the results of reliability analysis of power cables are compared when the cables are considered as repairable or non-repairable components. The paper demonstrates that the methods which estimate the time-to-the-first failure (for non-repairable components) lead to incorrect conclusions about reliability of repairable power cables.The proposed method is used to evaluate the failure rate of each individual Paper Insulated Lead Cover (PILC) underground cables in a distribution grid in the south of Sweden.

Ämnesord

TEKNIK OCH TEKNOLOGIER  -- Elektroteknik och elektronik -- Annan elektroteknik och elektronik (hsv//swe)
ENGINEERING AND TECHNOLOGY  -- Electrical Engineering, Electronic Engineering, Information Engineering -- Other Electrical Engineering, Electronic Engineering, Information Engineering (hsv//eng)
TEKNIK OCH TEKNOLOGIER  -- Elektroteknik och elektronik (hsv//swe)
ENGINEERING AND TECHNOLOGY  -- Electrical Engineering, Electronic Engineering, Information Engineering (hsv//eng)

Nyckelord

Power cable
historical data
reliability
proportional hazard model
preventive maintenance
Electrical Engineering
Elektro- och systemteknik

Publikations- och innehållstyp

ref (ämneskategori)
art (ämneskategori)

Hitta via bibliotek

Till lärosätets databas

Sök utanför SwePub

Kungliga biblioteket hanterar dina personuppgifter i enlighet med EU:s dataskyddsförordning (2018), GDPR. Läs mer om hur det funkar här.
Så här hanterar KB dina uppgifter vid användning av denna tjänst.

 
pil uppåt Stäng

Kopiera och spara länken för att återkomma till aktuell vy