Optimal sizing of the wind farm and wind farm transformer using MILP and dynamic transformer rating

Molina Gómez, Andrea (författare)
Morozovska, Kateryna, 1992- (författare)
KTH,Elektroteknisk teori och konstruktion,QED Asset Management group
Laneryd, Tor (författare)
KTH,Elektroteknik
visa fler...
Hilber, Patrik, 1975- (författare)
KTH,Elektroteknisk teori och konstruktion
visa färre...
 (creator_code:org_t)
Elsevier BV, 2022
2022
Engelska.
Ingår i: International Journal of Electrical Power & Energy Systems. - : Elsevier BV. - 0142-0615 .- 1879-3517. ; 136, s. 107645-107645
  • Tidskriftsartikel (refereegranskat)
Abstract Ämnesord
Stäng  
  • An increase in electricity demand and renewable penetration requires electrical utilities to improve and optimize the grid infrastructure. Fundamental components in this grid infrastructure are transformers, which are designed conservatively based on static rated power. However, load and weather change continuously and hence, transformers are not used most efficiently. For this reason, new technology has been developed: Dynamic transformer rating (DTR). Applying DTR makes it possible to load transformers above the nameplate rating without affecting their lifetime expectancy. This study uses DTR for short-term and long-term wind farm planning. The optimal wind farm is designed by applying DTR to the power transformer and using it as an input to a Mixed-Integer Linear Programming (MILP) model. Regarding the transformer thermal analysis, the linearized top oil model of IEEE Clause 7 is selected. The model is executed for 4 different types of power transformers: 63 MVA, 100 MVA, 200 MVA and 400 MVA. As a result, it is obtained that the net present value for the investment and the capacity of the wind farm increase linearly with respect to the size of the transformer. Then, a sensitivity analysis is carried out by modifying the wind speed, the electricity price, the lifetime of the transformer and the selected weather data. From this sensitivity analysis, it is possible to conclude that wind resources and electricity price are critical parameters for the wind farm’s feasibility.

Ämnesord

TEKNIK OCH TEKNOLOGIER  -- Elektroteknik och elektronik -- Annan elektroteknik och elektronik (hsv//swe)
ENGINEERING AND TECHNOLOGY  -- Electrical Engineering, Electronic Engineering, Information Engineering -- Other Electrical Engineering, Electronic Engineering, Information Engineering (hsv//eng)

Nyckelord

Electrical and Electronic Engineering
Energy Engineering and Power Technology
Electrical Engineering
Elektro- och systemteknik

Publikations- och innehållstyp

ref (ämneskategori)
art (ämneskategori)

Hitta via bibliotek

Till lärosätets databas

Sök utanför SwePub

Kungliga biblioteket hanterar dina personuppgifter i enlighet med EU:s dataskyddsförordning (2018), GDPR. Läs mer om hur det funkar här.
Så här hanterar KB dina uppgifter vid användning av denna tjänst.

 
pil uppåt Stäng

Kopiera och spara länken för att återkomma till aktuell vy