SwePub
Sök i LIBRIS databas

  Utökad sökning

id:"swepub:oai:DiVA.org:kth-32115"
 

Sökning: id:"swepub:oai:DiVA.org:kth-32115" > Decentralized cooli...

Decentralized cooling in district heating network : System simulation and parametric study

Udomsri, Seksan (författare)
KTH,Kraft- och värmeteknologi
Bales, Chris (författare)
Högskolan Dalarna,Energi och miljöteknik
Martin, Andrew R. (författare)
KTH,Kraft- och värmeteknologi
visa fler...
Martin, Viktoria (författare)
KTH,Kraft- och värmeteknologi
visa färre...
 (creator_code:org_t)
Elsevier, 2012
2012
Engelska.
Ingår i: Applied Energy. - : Elsevier. - 0306-2619 .- 1872-9118. ; 92, s. 175-184
  • Tidskriftsartikel (refereegranskat)
Abstract Ämnesord
Stäng  
  • This paper presents system simulation and parametric study of the demonstration system of decentralized cooling in district heating network. The monitoring results obtained from the demonstration were calibrated and used for parametric studies in order to find improved system design and control. This study concentrates on system simulation studies that aim to: reduce the electricity consumption, to improve the thermal COP's and capacity if possible; and to study how the system would perform with different boundary conditions such as climate and load. The internal pumps inside the thermally driven chiller (TDC) have been removed in the new version TDC and implemented in this study to increase the electrical COP. Results show that replacement of the fourth with the fifth generation TDC increases the system electrical COP from 2.64 to 5.27. The results obtained from parametric studies show that the electrical and thermal COP's, with new realistic boundary conditions, increased from 2.74 to 5.53 and 0.48 to 0.52, respectively for the 4th generation TDC and from 5.01 to 7.46 and 0.33 to 0.43, respectively for the 5th generation TDC. Additionally the delivered cold increased from 2320 to 8670 and 2080 to 7740. kWh for the 4th and 5th generation TDC's, respectively.

Ämnesord

TEKNIK OCH TEKNOLOGIER  -- Maskinteknik -- Energiteknik (hsv//swe)
ENGINEERING AND TECHNOLOGY  -- Mechanical Engineering -- Energy Engineering (hsv//eng)

Nyckelord

Decentralized cooling
District heating network
Simulation study
Thermally driven chiller
TRNSYS
Mechanical and thermal engineering
Mekanisk och termisk energiteknik
PolySMART

Publikations- och innehållstyp

ref (ämneskategori)
art (ämneskategori)

Hitta via bibliotek

Till lärosätets databas

Sök utanför SwePub

Kungliga biblioteket hanterar dina personuppgifter i enlighet med EU:s dataskyddsförordning (2018), GDPR. Läs mer om hur det funkar här.
Så här hanterar KB dina uppgifter vid användning av denna tjänst.

 
pil uppåt Stäng

Kopiera och spara länken för att återkomma till aktuell vy