Impacts of heat recovery ventilators on energy savings and indoor radon level

Akbari, Keramatollah (författare)
Mälardalens högskola,Akademin för ekonomi, samhälle och teknik
Öman, Robert, 1957- (författare)
Mälardalens högskola,Akademin för ekonomi, samhälle och teknik,Mälardalens universitet, Framtidens energi
 (creator_code:org_t)
2013
2013
Engelska.
Ingår i: Management of environmental quality. - 1477-7835 .- 1758-6119. ; 24:5, s. 682-694
  • Tidskriftsartikel (refereegranskat)
Abstract Ämnesord
Stäng  
  • Purpose: This paper aims to investigate the impact of heat recovery ventilators (HRVs) on the energy use and indoor radon in a one family detached house. Heat recovery ventilation systems, because of reducing ventilation loss through recovered exhaust air, can play a good role in the effectiveness of ventilation to reduce energy use. In addition HRVs can maintain pressure balance and outdoor ventilation rate at a required level to mitigate indoor radon level. Design/methodology/approach: In this study, a multizone model of a detached house is developed in IDA Indoor Climate and Energy (IDA ICE 4.0). The model is validated using measurements regarding use of energy for heating, ventilation and whole energy use. The performance of the heat recovery ventilation system is examined with respect to radon mitigation and energy saving by measuring the radon concentration and analyzing the life cycle cost of a heat exchanger unit. Findings: The results of the measurements and dynamic simulation showed that the heat recovery ventilation system could lead to 74 per cent energy savings of the ventilation loss, amounting to about 30 kWh m-2 per year. Life cycle cost analysis used for assessing total costs and the result showed that using this system is quite cost-effective and investment would payback during 12 years. Research limitations/implications: Limitations of this study generally refer to radon measurement and simulation because of radon complex behavior and its high fluctuations even during short periods of time. Practical implications: Heat recovery ventilation systems with reducing radon concentration improve indoor air quality and decrease environmental problems with energy savings. Social implications: Using balanced heat recovery ventilation can have benefits from the viewpoint of environmental impacts and household economy. Originality/value: Employment of a heat recovery unit to control indoor radon level is a new usage of this technology which along with energy savings can improve sustainable development.

Publikations- och innehållstyp

ref (ämneskategori)
art (ämneskategori)

Hitta via bibliotek

Till lärosätets databas

Hitta mer i SwePub

Av författaren/redakt...
Akbari, Keramato ...
Öman, Robert, 19 ...
Artiklar i publikationen
Management of en ...
Av lärosätet
Mälardalens universitet

Sök utanför SwePub

Kungliga biblioteket hanterar dina personuppgifter i enlighet med EU:s dataskyddsförordning (2018), GDPR. Läs mer om hur det funkar här.
Så här hanterar KB dina uppgifter vid användning av denna tjänst.

 
pil uppåt Stäng

Kopiera och spara länken för att återkomma till aktuell vy