Large Scale Tunnel Fire Tests with Large Droplet Water-Based Fixed Fire Fighting System

Ingason, Haukur (författare)
RISE,SP Fire Research
Li, Ying Zhen (författare)
RISE,SP – Sveriges Tekniska Forskningsinstitut
Appel, Glenn (författare)
Swedish Transport Administration, Sweden
visa fler...
Lundström, Ulf (författare)
Swedish Transport Administration, Sweden
Becker, Conny (författare)
Brandskyddslaget AB, Sweden
visa färre...
 (creator_code:org_t)
2015-03-22
2016
Engelska.
Ingår i: Fire technology. - : Springer Science and Business Media LLC. - 0015-2684 .- 1572-8099. ; 52:5, s. 1539-1558
  • Tidskriftsartikel (refereegranskat)
Abstract Ämnesord
Stäng  
  • This paper presents the main results of six large scale fixed fire fighting system tests that were carried out in the Runehamar tunnel in September 2013. It describes the background and the performance of the system. The main fire load consisted of 420 standardized wood pallets and a target consisting of a pile of 21 wood pallets placed 5 m from the rear end of the main fire load. The purpose was to investigate possible fire spread. The water spray system is a deluge zone system delivering 10 mm/min in the activated zone. The detection system was simulated with use of thermocouple in the tunnel ceiling. The alarm was registered when the ceiling gas temperature was 141°C. After alarm was obtained the system was activated manually after a given delay time that was varied in the tests. The heat release rates in tests with fire suppression were reduced to 20–45 MW compared to 100 MW estimated for a free-burn test or 75 MW in test 6 with a failure of activation. Fire spread to the target was prevented after fire suppression. 

Nyckelord

FFFS
Heat release rate
Large scale fire tests
Nozzle
Temperature
Water spray
Fire extinguishers
Fire fighting equipment
Flammability testing
Nozzles
Pallets
Piles
Spray nozzles
Testing
Thermocouples
Tunnel linings
Activated zones
Detection system
Fire fighting systems
Fire suppression
Heat Release Rate (HRR)
Water sprays
Fires

Publikations- och innehållstyp

ref (ämneskategori)
art (ämneskategori)

Hitta via bibliotek

Till lärosätets databas

Hitta mer i SwePub

Av författaren/redakt...
Ingason, Haukur
Li, Ying Zhen
Appel, Glenn
Lundström, Ulf
Becker, Conny
Artiklar i publikationen
Fire technology
Av lärosätet
RISE

Sök utanför SwePub

Kungliga biblioteket hanterar dina personuppgifter i enlighet med EU:s dataskyddsförordning (2018), GDPR. Läs mer om hur det funkar här.
Så här hanterar KB dina uppgifter vid användning av denna tjänst.

 
pil uppåt Stäng

Kopiera och spara länken för att återkomma till aktuell vy