Sökning: id:"swepub:oai:DiVA.org:ri-32445" >
Analysis of Muskö t...
Analysis of Muskö tunnel fire flows with automatic sprinkler activation
-
- Li, Ying Zhen (författare)
- RISE,Safety,Tunnel and Underground Safety Center
-
- Ingason, Haukur (författare)
- RISE,Safety,Tunnel and Underground Safety Center
-
(creator_code:org_t)
- ISBN 9789188695161
- Borås, 2017
- Engelska 30 s.
- Relaterad länk:
-
https://ri.diva-port... (primary) (Raw object)
-
visa fler...
-
https://urn.kb.se/re...
-
visa färre...
Abstract
Ämnesord
Stäng
- The focus of the present study is analyzing the best position of a sprinkler nozzle in a tunnel cross-section in the Muskö tunnel, south of Stockholm, Sweden. Activation of the sprinklers installed along the centerline and along the sidewall is investigated through analysis of full scale experiments and by three dimensional numerical modelling. Then the tunnel velocity is analyzed by one dimensional numerical modelling for various fire locations in the Muskö tunnel. For both activating the automatic sprinklers nearby the fire and avoiding activation of the sprinklers further downstream, the automatic sprinklers are recommended to be installed along the centerline of the tunnel. It has also been found that the tunnel velocity varies significantly with the fire location. When the fire is on the left side of the tunnel, the flow velocity mostly remains in a range of 1 m/s (positive or negative) within the first 10 minutes, which helps early activation of the automatic sprinklers. When the fire is on the right side of the tunnel, the flow velocity mostly remains within a range of -1 m/s and 1 m/s within the first 5 minutes, and the velocity mostly increases to 2 m/s at around 10 min. Therefore, the scenario for fire located on the left side is better than that for fire on the right side, especially when it is located between the middle of the right section and the right portal. As one typical case with fire on the right side, the tunnel velocity maintains at 1 m/s for the first 5 min and gradually increases to 2 m/s at 10 min. Under such conditions, the automatic sprinkler system is expected to perform well.
Ämnesord
- TEKNIK OCH TEKNOLOGIER -- Kemiteknik -- Kemiska processer (hsv//swe)
- ENGINEERING AND TECHNOLOGY -- Chemical Engineering -- Chemical Process Engineering (hsv//eng)
- TEKNIK OCH TEKNOLOGIER -- Samhällsbyggnadsteknik -- Husbyggnad (hsv//swe)
- ENGINEERING AND TECHNOLOGY -- Civil Engineering -- Building Technologies (hsv//eng)
- TEKNIK OCH TEKNOLOGIER -- Samhällsbyggnadsteknik -- Infrastrukturteknik (hsv//swe)
- ENGINEERING AND TECHNOLOGY -- Civil Engineering -- Infrastructure Engineering (hsv//eng)
- TEKNIK OCH TEKNOLOGIER -- Samhällsbyggnadsteknik -- Transportteknik och logistik (hsv//swe)
- ENGINEERING AND TECHNOLOGY -- Civil Engineering -- Transport Systems and Logistics (hsv//eng)
- TEKNIK OCH TEKNOLOGIER -- Maskinteknik -- Strömningsmekanik och akustik (hsv//swe)
- ENGINEERING AND TECHNOLOGY -- Mechanical Engineering -- Fluid Mechanics and Acoustics (hsv//eng)
Nyckelord
- tunnel fire
- tunnel velocity
- automatic sprinkler
- activation
Publikations- och innehållstyp