A numerical comparison of protective measures againstexternal fire spread

Nilsson, Markus (författare)
Brandskyddslaget AB, Sweden
Husted, Bjarne (författare)
Lund University,Lunds universitet,Avdelningen för Brandteknik,Institutionen för bygg- och miljöteknologi,Institutioner vid LTH,Lunds Tekniska Högskola,Division of Fire Safety Engineering,Department of Building and Environmental Technology,Departments at LTH,Faculty of Engineering, LTH
Mossberg, Axel (författare)
Lund University,Lunds universitet,Avdelningen för Brandteknik,Institutionen för bygg- och miljöteknologi,Institutioner vid LTH,Lunds Tekniska Högskola,Division of Fire Safety Engineering,Department of Building and Environmental Technology,Departments at LTH,Faculty of Engineering, LTH
visa fler...
Anderson, Johan (författare)
RISE,Safety,SP Swedish National Testing and Research Institute
Jansson Mcnamee, Robert (författare)
Brandskyddslaget AB, Sweden
visa färre...
 (creator_code:org_t)
2018-04-30
2018
Engelska.
Ingår i: Fire and Materials. - : John Wiley & Sons. - 0308-0501 .- 1099-1018. ; 42:5, s. 493-507
  • Tidskriftsartikel (refereegranskat)
Abstract Ämnesord
Stäng  
  • The impact of different passive protective measures against external vertical firespread was investigated using the numerical tool Fire Dynamics Simulator (FDS).The numerical study was divided into a validation study and a comparative analysis.The validation study was performed to evaluate FDS as a calculation tool for modellingexternal vertical fire spread and was conducted using experimental results from alarge‐scale fire test done on a SP FIRE 105 test rig at SP, Sweden. It was concludedthat FDS 6.2.0 could reproduce the experimental results with a reasonable level ofdetail. In the comparative analysis, the impact on the external fire from a smallerapartment was studied in FDS with different configurations of horizontal projectionsand spandrels in the building exterior. Also, the effects of an upper and lower facadeset‐back configuration were studied. The results show that facade solutions based ona horizontal projection or an upper facade set‐back configuration result in comparableor better protection compared with a defined spandrel height. The results also showthat a spandrel height of at least 1.2 m can be replaced by a 60‐cm‐deep horizontalprojection, given that the balcony is wider than the underlying opening.

Ämnesord

TEKNIK OCH TEKNOLOGIER  -- Samhällsbyggnadsteknik (hsv//swe)
ENGINEERING AND TECHNOLOGY  -- Civil Engineering (hsv//eng)
TEKNIK OCH TEKNOLOGIER  -- Samhällsbyggnadsteknik -- Annan samhällsbyggnadsteknik (hsv//swe)
ENGINEERING AND TECHNOLOGY  -- Civil Engineering -- Other Civil Engineering (hsv//eng)

Nyckelord

external fire spread
facade set‐back
FDS
fire safety engineering
horizontal projection
spandrel
External fire spread
Facade set-back
FDS
Fire safety engineering
Horizontal projection
Spandrel

Publikations- och innehållstyp

ref (ämneskategori)
art (ämneskategori)

Hitta via bibliotek

Till lärosätets databas

Sök utanför SwePub

Kungliga biblioteket hanterar dina personuppgifter i enlighet med EU:s dataskyddsförordning (2018), GDPR. Läs mer om hur det funkar här.
Så här hanterar KB dina uppgifter vid användning av denna tjänst.

 
pil uppåt Stäng

Kopiera och spara länken för att återkomma till aktuell vy