Sökning: id:"swepub:oai:lup.lub.lu.se:4bd1c41e-cae7-4789-9ccd-236d81c7ee03" >
Heat and Humidity T...
Heat and Humidity Transport Analysis Inside a Special Underground Building
-
Ai, Jian (författare)
-
Xue, Jie (författare)
-
- Yu, Jiabang (författare)
- Xi'an Jiaotong University
-
visa fler...
-
- Huang, Xinyu (författare)
- Xi'an Jiaotong University
-
- Wei, Pan (författare)
- Xi'an Jiaotong University
-
- Yang, Xiaohu (författare)
- Xi'an Jiaotong University
-
- Sundén, Bengt (författare)
- Lund University,Lunds universitet,NanoLund: Centre for Nanoscience,Annan verksamhet, LTH,Lunds Tekniska Högskola,Värmeöverföring,Institutionen för energivetenskaper,Institutioner vid LTH,LTH profilområde: Nanovetenskap och halvledarteknologi,LTH profilområden,Other operations, LTH,Faculty of Engineering, LTH,Heat Transfer,Department of Energy Sciences,Departments at LTH,Faculty of Engineering, LTH,LTH Profile Area: Nanoscience and Semiconductor Technology,LTH Profile areas,Faculty of Engineering, LTH
-
visa färre...
-
(creator_code:org_t)
- 2023
- 2023
- Engelska 17 s.
-
Ingår i: Frontiers in Heat and Mass Transfer. - 2151-8629. ; 21, s. 47-63
- Relaterad länk:
-
http://dx.doi.org/10... (free)
-
visa fler...
-
https://lup.lub.lu.s...
-
https://doi.org/10.3...
-
visa färre...
Abstract
Ämnesord
Stäng
- The calculation of heat and humidity load serves as the cornerstone of Heating, Ventilation, and Air Conditioning (HVAC) design. Nevertheless, as the heat and humidity load characteristics of underground structures differ substantially from those of above-ground structures, it is a challenge to derive their accurate calculation procedure through engineering experience. Therefore, it is particularly important to carry out quantitative research on heat and humidity load. This study used Design Builder software to study the inf luence of the design state point of air conditioning in underground buildings on energy consumption. The study showed that compared with the single design temperature of 18°C, setting the temperature of 16°C in winter and 22°C in summer could reduce energy consumption by about 59%. And the hourly heat load, cooling load and humidity load in one year are simulated and calculated so as to quantitatively analyze the characteristics of the load. This provides a database for selecting suitable HVAC equipment. It is further emphasized that dehumidification is the key to HVAC design of underground structures, which provides a reference for similar engineering designs.
Ämnesord
- TEKNIK OCH TEKNOLOGIER -- Maskinteknik -- Energiteknik (hsv//swe)
- ENGINEERING AND TECHNOLOGY -- Mechanical Engineering -- Energy Engineering (hsv//eng)
Nyckelord
- Design Builder
- energy consumption
- Heat and humidity load