SwePub
Sök i LIBRIS databas

  Utökad sökning

id:"swepub:oai:research.chalmers.se:40763b8b-8fe6-4bcd-bc20-ee24bfedc857"
 

Sökning: id:"swepub:oai:research.chalmers.se:40763b8b-8fe6-4bcd-bc20-ee24bfedc857" > Measured and percei...

Measured and perceived IEQ under different ventilation strategies in Swedish classrooms

Cabovska, Blanka, 1990 (författare)
Chalmers tekniska högskola,Chalmers University of Technology
Giraldo, Natalia (författare)
Danmarks Tekniske Universitet,Technical University of Denmark
Teli, Despoina, 1980 (författare)
Chalmers tekniska högskola,Chalmers University of Technology
visa fler...
Dalenbäck, Jan-Olof, 1954 (författare)
Chalmers tekniska högskola,Chalmers University of Technology
Beko, Gabriel (författare)
Danmarks Tekniske Universitet,Technical University of Denmark
Wargocki, Pawel (författare)
Danmarks Tekniske Universitet,Technical University of Denmark
Ekberg, Lars, 1962 (författare)
Chalmers tekniska högskola,Chalmers University of Technology
Langer, Sarka, 1960 (författare)
Chalmers tekniska högskola,Chalmers University of Technology
visa färre...
 (creator_code:org_t)
2022
2022
Engelska.
Ingår i: 17th International Conference on Indoor Air Quality and Climate, INDOOR AIR 2022.
  • Konferensbidrag (refereegranskat)
Abstract Ämnesord
Stäng  
  • Indoor environmental quality was assessed in Swedish primary school classrooms grouped into three categories based on the ventilation system: 1) natural or exhaust ventilation, 2) balanced mechanical ventilation systems with constant air volume (CAV), 3) balanced mechanical ventilation systems with variable air volume (VAV). Measurements of NO2, ozone, TVOC, formaldehyde, PM10, and PM2.5 and a questionnaire survey were conducted. The concentrations of pollutants were integrated into Indoor Air Pollution Index allowing the rank comparison of classrooms. Children’s perception scores were calculated based on the questionnaire responses. Naturally ventilated classrooms had higher level of air pollution. No significant differences in pollutant levels were observed between classrooms with CAV and VAV systems. The type of ventilation system affected the subjective assessment of indoor air quality; it was worst in naturally ventilated classrooms.

Ämnesord

TEKNIK OCH TEKNOLOGIER  -- Samhällsbyggnadsteknik -- Arkitekturteknik (hsv//swe)
ENGINEERING AND TECHNOLOGY  -- Civil Engineering -- Architectural Engineering (hsv//eng)
TEKNIK OCH TEKNOLOGIER  -- Samhällsbyggnadsteknik (hsv//swe)
ENGINEERING AND TECHNOLOGY  -- Civil Engineering (hsv//eng)
TEKNIK OCH TEKNOLOGIER  -- Samhällsbyggnadsteknik -- Husbyggnad (hsv//swe)
ENGINEERING AND TECHNOLOGY  -- Civil Engineering -- Building Technologies (hsv//eng)

Nyckelord

questionnaire
perception score
indoor air pollution index
Indoor air pollutants

Publikations- och innehållstyp

kon (ämneskategori)
ref (ämneskategori)

Till lärosätets databas

Sök utanför SwePub

Kungliga biblioteket hanterar dina personuppgifter i enlighet med EU:s dataskyddsförordning (2018), GDPR. Läs mer om hur det funkar här.
Så här hanterar KB dina uppgifter vid användning av denna tjänst.

 
pil uppåt Stäng

Kopiera och spara länken för att återkomma till aktuell vy