Global monitoring of fluidized-bed processes by means of microwave cavity resonances

Nohlert, Johan, 1987 (författare)
Chalmers tekniska högskola,Chalmers University of Technology
Cerullo, Livia, 1982 (författare)
Chalmers tekniska högskola,Chalmers University of Technology
WINGES, JOHAN, 1987 (författare)
Chalmers tekniska högskola,Chalmers University of Technology
visa fler...
Rylander, Thomas, 1972 (författare)
Chalmers tekniska högskola,Chalmers University of Technology
McKelvey, Tomas, 1966 (författare)
Chalmers tekniska högskola,Chalmers University of Technology
Holmgren, A. (författare)
AstraZeneca AB
Gradinarsky, Lubomir, 1970 (författare)
AstraZeneca AB
Folestad, Staffan (författare)
AstraZeneca AB
Viberg, Mats, 1961 (författare)
Chalmers tekniska högskola,Chalmers University of Technology
Rasmuson, Anders, 1951 (författare)
Chalmers tekniska högskola,Chalmers University of Technology
visa färre...
 (creator_code:org_t)
Elsevier BV, 2014
2014
Engelska.
Ingår i: Measurement: Journal of the International Measurement Confederation. - : Elsevier BV. - 0263-2241. ; 55, s. 520-535
  • Tidskriftsartikel (refereegranskat)
Abstract Ämnesord
Stäng  
  • We present an electromagnetic measurement system for monitoring of the effective permittivity in closed metal vessels, which are commonly used in the process industry. The measurement system exploits the process vessel as a microwave cavity resonator and the relative change in its complex resonance frequencies is related to the complex effective permittivity inside the vessel. Also, thermal expansion of the process vessel is taken into account and we compensate for its influence on the resonance frequencies by means of a priori information derived from a set of temperature measurements. The sensitivities, that relate the process state to the measured resonance frequencies, are computed by means of a detailed finite element model. The usefulness of the proposed measurement system is successfully demonstrated for a pharmaceutical fluidized-bed process, where the water and solid contents inside the process vessel is of interest.

Ämnesord

TEKNIK OCH TEKNOLOGIER  -- Elektroteknik och elektronik -- Signalbehandling (hsv//swe)
ENGINEERING AND TECHNOLOGY  -- Electrical Engineering, Electronic Engineering, Information Engineering -- Signal Processing (hsv//eng)

Nyckelord

Permittivity estimation
Electromagnetic homogenization
Sensitivity analysis
Pharmaceutical fluidized-bed process
Finite element method
Microwave measurement system

Publikations- och innehållstyp

art (ämneskategori)
ref (ämneskategori)

Hitta via bibliotek

Till lärosätets databas

Kungliga biblioteket hanterar dina personuppgifter i enlighet med EU:s dataskyddsförordning (2018), GDPR. Läs mer om hur det funkar här.
Så här hanterar KB dina uppgifter vid användning av denna tjänst.

 
pil uppåt Stäng

Kopiera och spara länken för att återkomma till aktuell vy