Dynamic State Estimation based Transmission Line Protection Scheme: Performance Evaluation with Different Fault Types and Conditions
-
- Srivastava, Ankur, 1989 (författare)
- Chalmers tekniska högskola,Chalmers University of Technology
-
- Le, Anh Tuan, 1974 (författare)
- Chalmers tekniska högskola,Chalmers University of Technology
-
- Steen, David, 1983 (författare)
- Chalmers tekniska högskola,Chalmers University of Technology
-
visa fler...
-
- Carlson, Ola, 1955 (författare)
- Chalmers tekniska högskola,Chalmers University of Technology
-
Bijwaard, Dennis (författare)
-
Mansour, Omar (författare)
-
visa färre...
-
(creator_code:org_t)
- Elsevier BV, 2023
- 2023
- Engelska.
-
Ingår i: International Journal of Electrical Power and Energy Systems. - : Elsevier BV. - 0142-0615. ; 148
- Relaterad länk:
-
https://research.cha... (primary) (free)
-
visa fler...
-
https://research.cha...
-
https://doi.org/10.1...
-
visa färre...
Abstract
Ämnesord
Stäng
- This paper presents the experimental validation of a transmission line protection scheme based on dynamic state estimation for different fault types and conditions. The protection scheme utilizes real-time high-frequency sampled measurements from advanced sensors and evaluates the operating condition of the transmission line based on which a tripping signal is generated in case a fault occurs. The validation is performed using a physical scaled-down model of a power system, consisting of a transmission line, transformer, synchronous generator, and loads. The following faults are examined during the validation: unbalanced faults under different load conditions, high impedance fault, fault current fed from both ends, hidden failure, external fault, and load change conditions. The results show that the scheme performs as intended and thus proves its efficacy to detect various types of faults. The maximum fault detection time is calculated to be 42.5 milliseconds, while the maximum fault clearing time comes out to be 82.5 milliseconds, on par with currently employed protection methods. The obtained results demonstrate the ability of the scheme to detect different fault types under varying conditions and avoid potential issues with relay coordination
Ämnesord
- TEKNIK OCH TEKNOLOGIER -- Elektroteknik och elektronik (hsv//swe)
- ENGINEERING AND TECHNOLOGY -- Electrical Engineering, Electronic Engineering, Information Engineering (hsv//eng)
Nyckelord
- high impedance fault
- hidden failures
- Dynamic state estimation
- setting-less protection
- transmission line protection
- experimental validation