Transformers internal voltage stress during current interruption for different wind turbine layouts

Abdulahovic, Tarik, 1976 (författare)
Chalmers tekniska högskola,Chalmers University of Technology
Thiringer, Torbjörn, 1966 (författare)
Chalmers tekniska högskola,Chalmers University of Technology
 (creator_code:org_t)
ISBN 9781479901166
2013
2013
Engelska.
Ingår i: 2013 15th European Conference on Power Electronics and Applications, EPE 2013. - 9781479901166 ; , s. no. 6634759-
  • Konferensbidrag (refereegranskat)
Abstract Ämnesord
Stäng  
  • The voltage transients generated during the breaker operations in cable systems, for instance, a wind park collection grid, can reach very low rise times. The rise times of these transients can be almost 50 times shorter than the rise time of a lightning pulse. Such transients can generate a very high voltage stress on the internal transformers insulation. In this paper, a test case is studied using verified models of different types of transformers and wind turbine layouts in order to account for typical wind turbine layouts found in modern wind farms. A critical switching scenario is chosen in order to provoke the highest possible voltage transients during a current interruption. Furthermore, internal overvoltages are estimated using model of a similarly sized winding. Simulations show that the magnitude of the voltage transients is higher than the basic lightning impulse insulation level (BIL) defined by present standards. Moreover, it is found that the rise time of the voltage surges is much shorter than the rise time of the lightning pulse. The shortest rise time of 40ns is obtained in a wind turbine layout where the wind turbine breaker is placed near the transformer. Due to very short rise times of the transients, very high internal overvoltages are estimated in dry-type transformer windings. These internal overvoltages are much higher than overvoltages recorded at the basic lightning impulse level. For a wind turbine layout where a breaker is placed in the bottom of a tower and a dry-type transformer in a nacelle, the highest turn-to-turn voltage of about 1.5pu is estimated. This is almost 4 times higher turn-to-turn voltage then the voltage obtained during the BIL test. In a wind turbine layout where a breaker is placed close to the transformer, the amplitude of the turn-to-turn voltages reached 1.8pu due to lower stray capacitances and thus a shorter rise time of voltage strikes.

Ämnesord

TEKNIK OCH TEKNOLOGIER  -- Elektroteknik och elektronik (hsv//swe)
ENGINEERING AND TECHNOLOGY  -- Electrical Engineering, Electronic Engineering, Information Engineering (hsv//eng)
TEKNIK OCH TEKNOLOGIER  -- Elektroteknik och elektronik -- Annan elektroteknik och elektronik (hsv//swe)
ENGINEERING AND TECHNOLOGY  -- Electrical Engineering, Electronic Engineering, Information Engineering -- Other Electrical Engineering, Electronic Engineering, Information Engineering (hsv//eng)

Nyckelord

lightning impulse test
Transformer
Wind turbine
Surge
Very fast transient

Publikations- och innehållstyp

kon (ämneskategori)
ref (ämneskategori)

Hitta via bibliotek

Till lärosätets databas

Hitta mer i SwePub

Av författaren/redakt...
Abdulahovic, Tar ...
Thiringer, Torbj ...
Om ämnet
TEKNIK OCH TEKNOLOGIER
TEKNIK OCH TEKNO ...
och Elektroteknik oc ...
TEKNIK OCH TEKNOLOGIER
TEKNIK OCH TEKNO ...
och Elektroteknik oc ...
och Annan elektrotek ...
Artiklar i publikationen
2013 15th Europe ...
Av lärosätet
Chalmers tekniska högskola

Sök utanför SwePub

Kungliga biblioteket hanterar dina personuppgifter i enlighet med EU:s dataskyddsförordning (2018), GDPR. Läs mer om hur det funkar här.
Så här hanterar KB dina uppgifter vid användning av denna tjänst.

 
pil uppåt Stäng

Kopiera och spara länken för att återkomma till aktuell vy