Automated active fault detection in fouled dissolved oxygen sensors
- 2019
-
Ingår i: Water Research. - : PERGAMON-ELSEVIER SCIENCE LTD. - 0043-1354 .- 1879-2448. ; 166
-
Tidskriftsartikel (refereegranskat)abstract
- Biofilm formation causes bias in dissolved oxygen (DO) sensors, which hamper their usage for automatic control and thereby balancing energy- and treatment efficiency. We analysed if a dataset that was generated with deliberate perturbations, can automatically be interpreted to detect bias caused by biofilm formation. We used a challenging set-up with realistic conditions that are required for a full-scale application. This included automated training (adapting to changing normal conditions) and automated tuning (setting an alarm threshold) to assure that the fault detection (FD)-methods are accessible to the operators. The results showed that automatic usage of FD-methods is difficult, especially in terms of automatic tuning of alarm thresholds when small training datasets only represent the normal conditions, i.e. clean sensors. Despite the challenging set-up, two FD-methods successfully improved the detection limit to 0.5 mg DO/L bias caused by biofilm formation. We showed that the studied dataset could be interpreted equally well by simpler FD-methods, as by advanced machine learning algorithms. This in turn indicates that the information contained in the actively generated data was more vital than its interpretation by advanced algorithms.
|
|