SwePub
Sök i SwePub databas

  Utökad sökning

Träfflista för sökning "id:"swepub:oai:research.chalmers.se:f081572c-dbf5-444a-a9db-f6139b34a3df" "

Sökning: id:"swepub:oai:research.chalmers.se:f081572c-dbf5-444a-a9db-f6139b34a3df"

  • Resultat 1-1 av 1
Sortera/gruppera träfflistan
   
NumreringReferensOmslagsbildHitta
1.
  • Romano, Francesco, et al. (författare)
  • Numerical and experimental analysis of airborne particles control in an operating theater
  • 2015
  • Ingår i: Building and Environment. - : Elsevier BV. - 0360-1323. ; 89, s. 369-379
  • Tidskriftsartikel (refereegranskat)abstract
    • The design of a ventilation system for operating theaters (OT) is aimed to reduce the patient infection risk while maintaining adequate comfort and productivity for the surgical staff. Nowadays, Computational Fluid Dynamics (CFD) represents an important tool to simulate the airflow pattern in an operating theater and its ability to remove airborne particles. The CFD advantages, compared to experimental campaigns, consist in the ability to test different configurations, in the ease of implementation and in time and money savings. The aim of this work is to numerically and experimentally investigate an OT with a layout according to the Standard DIN 1946-4. Moreover the effectiveness of a differential airflow diffusion system on reducing the particle concentration above the operating table is analyzed. The supply air comes from a ceiling filter system composed of 23 H14 filters, which assures an unidirectional flow with differential air velocities over the protected area. In order to experimentally evaluate the performance and the protection grade SG, according to DIN 1946-4, and to validate the numerical results, a measuring campaign has been carried out within a laboratory setup of an OT. Two different scenarios have been adopted to evaluate the protection level against the entry of external and internal contaminant loads into the protected area. For both cases, the simulated and measured particle concentration in the protected area agree well, and the differential air flow diffusion system is able to maintain the desired protective effect (SG) against contamination load in both the design and the off-design conditions.
  •  
Skapa referenser, mejla, bekava och länka
  • Resultat 1-1 av 1
Typ av publikation
tidskriftsartikel (1)
Typ av innehåll
refereegranskat (1)
Författare/redaktör
Gusten, Jan, 1952 (1)
Romano, Francesco (1)
Joppolo, Cesare M. (1)
Marocco, Luca (1)
Lärosäte
Chalmers tekniska högskola (1)
Språk
Engelska (1)
Forskningsämne (UKÄ/SCB)
Teknik (1)
År

Kungliga biblioteket hanterar dina personuppgifter i enlighet med EU:s dataskyddsförordning (2018), GDPR. Läs mer om hur det funkar här.
Så här hanterar KB dina uppgifter vid användning av denna tjänst.

 
pil uppåt Stäng

Kopiera och spara länken för att återkomma till aktuell vy