2. |
- Carlsson, Bengt, et al.
(författare)
-
Fault detection of sensors in aeration control systems : the airflow ratio method
- 2013
-
Ingår i: 11th IWA conference on Instrumentation, Control and Automation.
-
Konferensbidrag (refereegranskat)abstract
- A fault detection method, ARM, has been proposed for detection of faults in DOsensors in a serie of aerated zones. The DO in each zone is assumed to be controlled. In a simulation study, ARM shows promising results for correct and early fault detection. Eventually, it will not be possible to distinguish between a fault in a DOsensor and in air flow rate sensor. In this study, we have, for simplicity, used KLa as a measure of the air flow rate. In practice an air flow rate sensor should be used. An interesting alternative is to use the air valve position instead of the airflow rate.
|
|