Sökning: id:"swepub:oai:research.chalmers.se:80e1c762-0e6d-4520-b2b6-8a0a1a23c030" >
Dielectric Response...
Dielectric Response Characterization of In-service Aged Sheds of (U) HVDC Silicone Rubber Composite Insulators
-
- Yuan, Chao (författare)
- South China University of Technology
-
- xie, congzhen (författare)
- South China University of Technology
-
- li, licheng (författare)
- South China University of Technology
-
visa fler...
-
- Xu, Xiangdong, 1984 (författare)
- Chalmers tekniska högskola,Chalmers University of Technology
-
- Gubanski, Stanislaw, 1950 (författare)
- Chalmers tekniska högskola,Chalmers University of Technology
-
- he, zilan (författare)
- China Southern Power Grid
-
visa färre...
-
(creator_code:org_t)
- 2016
- 2016
- Engelska.
-
Ingår i: IEEE Transactions on Dielectrics and Electrical Insulation. - 1558-4135 .- 1070-9878. ; 23:3, s. 1418-1426
- Relaterad länk:
-
http://dx.doi.org/10...
-
visa fler...
-
https://doi.org/10.1...
-
https://research.cha...
-
visa färre...
Abstract
Ämnesord
Stäng
- Investigations of bulk dielectric properties of specimens extracted from in-service aged and aged UHVDC composite insulator sheds are reported in this paper. The program of the study included measurements of DC conductivity and complex permittivity at frequency range 10-4 – 103 Hz at various temperatures in dry and wet (water immersion) conditions. The obtained results are analyzed by considering a combination of relations describing various dielectric relaxation modes in dielectrics, included three Cole-Cole types of responses and a hopping process. The hopping has the strongest impact on the responses in the whole frequency range. Two of the Cole- Cole responses appearing in the low frequency range are attributed to Maxwell- Wagner-Sillars relaxations at macroscopic and mesoscopic levels; first one representing interfacial polarization at the border between specimen and air gap in the electrode arrangement, while the second one is attributed to the charge relaxation at filler boundaries and internal cavities in the polymeric materials. The third Cole-Cole process, active at higher frequencies, is considered as a sign of polymer degradation, as it shifts with the ageing to higher frequencies.Based on the results of this study, it is claimed that dielectric response measurements on specimens of in-service aged composite insulator sheds can provide useful information on the degree of material degradation. In addition, a water immersion test in combination with such measurements may be a good way to enhancing the observed changes.
Ämnesord
- TEKNIK OCH TEKNOLOGIER -- Materialteknik (hsv//swe)
- ENGINEERING AND TECHNOLOGY -- Materials Engineering (hsv//eng)
- TEKNIK OCH TEKNOLOGIER -- Elektroteknik och elektronik (hsv//swe)
- ENGINEERING AND TECHNOLOGY -- Electrical Engineering, Electronic Engineering, Information Engineering (hsv//eng)
Nyckelord
- air reference method
- dielectric response
- contact-free electrode arrangement
- HVDC composite insulator
- ageing
Publikations- och innehållstyp
- art (ämneskategori)
- ref (ämneskategori)
Hitta via bibliotek