Sökning: onr:"swepub:oai:DiVA.org:ltu-67443" >
Effect of Working P...
Effect of Working Parameters of the Plate Heat Exchanger on the Thermal Performance of the Anti-Bact Heat Exchanger System to Disinfect Legionella in Hot Water Systems
-
- Altorkmany, Lobna (författare)
- Luleå tekniska universitet,Arkitektur och vatten,Luleå tekniska universitet (LTU),Luleå University of Technology (LTU)
-
- Kharseh, Mohamad, 1980 (författare)
- Civil Environmental Engineering Department, Chalmers University of Technology, Sweden,Chalmers tekniska högskola,Chalmers University of Technology
-
- Ljung, Anna-Lena (författare)
- Luleå tekniska universitet,Strömningslära och experimentell mekanik,Luleå tekniska universitet (LTU),Luleå University of Technology (LTU)
-
visa fler...
-
- Lundström, Staffan (författare)
- Luleå tekniska universitet,Strömningslära och experimentell mekanik,Luleå tekniska universitet (LTU),Luleå University of Technology (LTU)
-
visa färre...
-
(creator_code:org_t)
- Elsevier, 2018
- 2018
- Engelska.
-
Ingår i: Applied Thermal Engineering. - : Elsevier. - 1359-4311 .- 1873-5606. ; 141, s. 435-443
- Relaterad länk:
-
https://urn.kb.se/re...
-
visa fler...
-
https://doi.org/10.1...
-
https://research.cha...
-
visa färre...
Abstract
Ämnesord
Stäng
- The objective of the current study is to analyze the effect of different working parameters on the thermal performance of the Anti-Bact Heat Exchanger system (ABHE). The ABHE system is inspired by nature and implemented to achieve continuous disinfection of Legionella in different human-made water systems at any desired disinfection temperature. In the ABHE system, most of the energy is recovered using an efficient plate heat exchanger (PHE). A model by Engineering Equation Solver (EES) is set-up to figure out the effect of different working parameters on the thermal performance of the ABHE system. The study shows that higher supplied water temperature can enhance the regeneration ratio (RR), but it requires a large PHE area and pumping power (PP) which consequently increase the cost of the ABHE system. However, elevate temperature in use results in a reduced PHE area and PP, which accordingly reduce the cost of the ABHE system. On the other hand, the EES-based model is used to study the effect of the length and the width of the plates used in the PHE on the RR and the required area of the PHE. Finally, taking into account the geometrical parameters, flow arrangement and the initial operating conditions of the PHE, the EES-based model is used to optimize the PHE in which its area is minimized, and the RR of the ABHE system is maximized.
Ämnesord
- TEKNIK OCH TEKNOLOGIER -- Maskinteknik -- Strömningsmekanik och akustik (hsv//swe)
- ENGINEERING AND TECHNOLOGY -- Mechanical Engineering -- Fluid Mechanics and Acoustics (hsv//eng)
- TEKNIK OCH TEKNOLOGIER -- Maskinteknik -- Energiteknik (hsv//swe)
- ENGINEERING AND TECHNOLOGY -- Mechanical Engineering -- Energy Engineering (hsv//eng)
- TEKNIK OCH TEKNOLOGIER -- Naturresursteknik -- Energisystem (hsv//swe)
- ENGINEERING AND TECHNOLOGY -- Environmental Engineering -- Energy Systems (hsv//eng)
- TEKNIK OCH TEKNOLOGIER -- Elektroteknik och elektronik -- Annan elektroteknik och elektronik (hsv//swe)
- ENGINEERING AND TECHNOLOGY -- Electrical Engineering, Electronic Engineering, Information Engineering -- Other Electrical Engineering, Electronic Engineering, Information Engineering (hsv//eng)
Nyckelord
- Legionella
- thermal disinfection
- simulation
- thermal performance
- plate heat exchanger
- Strömningslära
- Fluid Mechanics
Publikations- och innehållstyp