Results of an International Comparison of Instrument Current Transformers up to 10 kA at 50 Hz Frequency
-
- Draxler, K. (författare)
- CTU, Czech Republic
-
- Styblikova, R. (författare)
- CMI, Czech Republic
-
- Hlavacek, J. (författare)
- CTU, Czech Republic
-
visa fler...
-
- Rietveld, G. (författare)
- VSL, Netherlands
-
- Van Den Brom, H. E. (författare)
- VSL, Netherlands
-
- Schnaitt, M. (författare)
- BEV, Austria
-
- Waldmann, W. (författare)
- BEV, Austria
-
- Dimitrov, E. (författare)
- BIM, Bulgaria
-
- Cincar-Vujovic, T. (författare)
- DMDM, Serbia
-
- Paczek, B. (författare)
- GUM, Poland
-
- Sadkowski, G. (författare)
- GUM, Poland
-
- Crotti, G. (författare)
- INRIM, Italy
-
- Martin, R. (författare)
- LCOE, Spain
-
- Garnacho, F. (författare)
- LCOE, Spain
-
- Blanc, I. (författare)
- LNE, France
-
- Kampfer, R. (författare)
- METAS, Switzerland
-
- Mester, C. (författare)
- METAS, Switzerland
-
- Wheaton, A. (författare)
- NPL, UK
-
- Mohns, E. (författare)
- PTB, Germany
-
- Bergman, Anders (författare)
- RISE,Mätteknik
-
- Hammarquist, Maria (författare)
- RISE,Mätteknik
-
- Cayci, H. (författare)
- UME, Turkey
-
- Hallstrom, J. (författare)
- VTT, Finland
-
- Suomalainen, E. -P (författare)
- VTT, Finland
-
visa färre...
-
(creator_code:org_t)
- 2018
- 2018
- Engelska.
-
Ingår i: CPEM 2018 - Conference on Precision Electromagnetic Measurements. - 9781538609736
- Relaterad länk:
-
https://urn.kb.se/re...
-
visa fler...
-
https://doi.org/10.1...
-
visa färre...
Abstract
Ämnesord
Stäng
- Traceability of the current ratio is crucial for the measurement of electrical energy in revenue metering. A comparison of the AC current ratio was therefore performed within EURAMET in the time period 2012-2016, using a precision CT as the traveling device. The Czech Metrology Institute (CMI) as coordinator processed the measurement results of the 15 European participating laboratories. The comparison of the results for transformer ratios of (4, 5, 6, 8, 10) kA 5 A at 15 VA burden and (4 and 10) kA 5 A ratios at 5 VA burden indicates good agreement between the participating laboratories. The main differences are found for phase displacement, at least in part due to instability of the traveling standard. .
Nyckelord
- comparison
- current measurement
- Current ratio
- current transformers (CT)
- high current
- instrument transformers
- phase displacement
- ratio error
- Electric current measurement
- Current ratios
- High currents
- Electric instrument transformers
Publikations- och innehållstyp
- ref (ämneskategori)
- kon (ämneskategori)
Hitta via bibliotek
Till lärosätets databas
- Av författaren/redakt...
-
Draxler, K.
-
Styblikova, R.
-
Hlavacek, J.
-
Rietveld, G.
-
Van Den Brom, H. ...
-
Schnaitt, M.
-
visa fler...
-
Waldmann, W.
-
Dimitrov, E.
-
Cincar-Vujovic, ...
-
Paczek, B.
-
Sadkowski, G.
-
Crotti, G.
-
Martin, R.
-
Garnacho, F.
-
Blanc, I.
-
Kampfer, R.
-
Mester, C.
-
Wheaton, A.
-
Mohns, E.
-
Bergman, Anders
-
Hammarquist, Mar ...
-
Cayci, H.
-
Hallstrom, J.
-
Suomalainen, E. ...
-
visa färre...
- Artiklar i publikationen
-
CPEM 2018 - Conf ...
- Av lärosätet
-
RISE