- A series of 1:3 intermediate scale tunnel fire tests was performed to investigate the performance of a fully automatic sprinkler system in a road tunnel. The experiments were carried in a container tunnel with scaled geometry, using wood pallets as the fire source to simulate HGV fires. The activation of the sprinklers was simulated by using thermocouples that corresponded to a given Thermal Response Index (RTI) of a sprinkler bulb or a link. A total of 12 tests were carried out with varying longitudinal velocities (0.8–1.7 m/s), sprinkler activation temperatures (68–141 °C), water densities (2.9–8.7 mm/min) and types of arrangement of the fuel. The activation times, number of activated sprinklers, maximum heat release rates and other key parameters are presented and analyzed. The results show that the water density plays a key role in the performance of the automatic sprinkler systems tested. A high tunnel ventilation velocity, low water density and low sprinkler activation temperature are not recommended. © 2022 The Authors
Ämnesord
- TEKNIK OCH TEKNOLOGIER -- Maskinteknik (hsv//swe)
- ENGINEERING AND TECHNOLOGY -- Mechanical Engineering (hsv//eng)
Nyckelord
- Activation
- Automatic sprinkler
- Model scale
- Tunnel fire
- Tunnel velocity
- Chemical activation
- Fires
- Flammability testing
- Sprinkler systems (irrigation)
- Thermocouples
- Activation temperatures
- Fire tests
- Performance
- Road tunnel
- Sprinkler activation
- Tunnel fires
- Water density
- Hose
Publikations- och innehållstyp
- ref (ämneskategori)
- art (ämneskategori)
Hitta via bibliotek
Till lärosätets databas