Position of maximum ceiling temperature in a tunnel fire

Li, Ying Zhen (författare)
Ingason, Haukur (författare)
RISE,SP – Sveriges Tekniska Forskningsinstitut / Brandteknik, skydd (BRs )
 (creator_code:org_t)
2012-11-27
2014
Engelska.
Ingår i: Fire technology. - : Springer Science and Business Media LLC. - 0015-2684 .- 1572-8099. ; 50:4, s. 889-905
  • Tidskriftsartikel (refereegranskat)
Abstract Ämnesord
Stäng  
  • The position of the maximum ceiling gas temperature indicates how far the fire plum could be blown away by a ventilation flow. It could be applied to estimate the activation of a detection system or a sprinkler system, or to estimate the range of damage to the tunnel structure. An equation for predicting the position of the maximum ceiling gas temperature in a tunnel fire is proposed based on a theoretical analysis and validated using both laboratory test data and full scale test data. A flame angle has been defined based on the position of the maximum ceiling temperature in a tunnel fire. The flame angle is directly related to the dimensionless ventilation velocity, and it becomes insensitive to the heat release rate for a large tunnel fire. Further, it is found that a constant critical flame angle exists, defined as the flame angle under the critical condition when the backlayering just disappears. For a given tunnel and fire source, the flame angle under critical conditions is the same value, independent of heat release rate, and the maximum ceiling temperature under critical conditions always corresponds to the same position. Generally the horizontal distance between the position of the maximum ceiling temperature and the fire source centre is around 1.5 times the effective tunnel height under the critical condition.

Publikations- och innehållstyp

ref (ämneskategori)
art (ämneskategori)

Hitta via bibliotek

Till lärosätets databas

Hitta mer i SwePub

Av författaren/redakt...
Li, Ying Zhen
Ingason, Haukur
Artiklar i publikationen
Fire technology
Av lärosätet
RISE

Sök utanför SwePub

Kungliga biblioteket hanterar dina personuppgifter i enlighet med EU:s dataskyddsförordning (2018), GDPR. Läs mer om hur det funkar här.
Så här hanterar KB dina uppgifter vid användning av denna tjänst.

 
pil uppåt Stäng

Kopiera och spara länken för att återkomma till aktuell vy