Sökning: onr:"swepub:oai:lup.lub.lu.se:12b7874d-1006-4512-8ac6-21c7fb173a1b" >
Dissolved oxygen co...
Dissolved oxygen controller based on on-line measurements of ammonium combining feed-forward and feedback
-
Ingildsen, P (författare)
-
- Jeppsson, Ulf (författare)
- Lund University,Lunds universitet,Industriell elektroteknik och automation,Institutionen för biomedicinsk teknik,Institutioner vid LTH,Lunds Tekniska Högskola,Industrial Electrical Engineering and Automation,Department of Biomedical Engineering,Departments at LTH,Faculty of Engineering, LTH
-
- Olsson, Gustaf (författare)
- Lund University,Lunds universitet,Industriell elektroteknik och automation,Institutionen för biomedicinsk teknik,Institutioner vid LTH,Lunds Tekniska Högskola,Industrial Electrical Engineering and Automation,Department of Biomedical Engineering,Departments at LTH,Faculty of Engineering, LTH
-
(creator_code:org_t)
- 2002
- 2002
- Engelska.
-
Ingår i: Water Science and Technology. - 0273-1223. ; 45:4-5, s. 453-460
- Relaterad länk:
-
http://www.iwaponlin...
-
visa fler...
-
http://www.iwaponlin...
-
https://lup.lub.lu.s...
-
https://lup.lub.lu.s...
-
visa färre...
Abstract
Ämnesord
Stäng
- As the largest single energy-consuming component in most biological wastewater treatment systems, control of aeration is of great interest seen from an energy savings point of view. This paper suggests a simple way of using on-line ammonium measurements to control aeration in a pre-denitrification plant by controlling the dissolved oxygen setpoint. The controller works primarily by feed-forward based on an ammonium sensor located at the head of the aerobic process part. Using online in-situ sensor measurements directly from the process have the important advantage over effluent measurements that there is no or very short time delay for information. The controller has been implemented in a full-scale wastewater treatment plant for a period of 35 days, During the experiment two identical activated sludge lines were used. The controller was implemented in one line, while the other line worked as a reference for comparison. The preliminary results indicate that the described control strategy leads to energy savings for the aeration in the region of 5-15%, while maintaining approximately the same effluent quality as in the reference line. Even higher energy savings can probably be achieved by optimising the controller. An automatic procedure for updating the controller parameters based on dynamic effluent ammonium measurement has been tested.
Ämnesord
- TEKNIK OCH TEKNOLOGIER -- Elektroteknik och elektronik -- Annan elektroteknik och elektronik (hsv//swe)
- ENGINEERING AND TECHNOLOGY -- Electrical Engineering, Electronic Engineering, Information Engineering -- Other Electrical Engineering, Electronic Engineering, Information Engineering (hsv//eng)
Nyckelord
- pre-denitrification plant
- full-scale
- control
- activated sludge process
- aeration
- nitrogen removal
- nutrient sensors
Publikations- och innehållstyp