The impact of a DCV...
The impact of a DCV-system on the IAQ, energy use, and moisture safety in apartments - a case study
-
- Abdul Hamid, Akram (författare)
- Lund University,Lunds universitet,Avdelningen för Byggnadsfysik,Institutionen för bygg- och miljöteknologi,Institutioner vid LTH,Lunds Tekniska Högskola,Division of Building Physics,Department of Building and Environmental Technology,Departments at LTH,Faculty of Engineering, LTH
-
- Johansson, Dennis (författare)
- Lund University,Lunds universitet,Avdelningen för Installations- och klimatiseringslära,Institutionen för bygg- och miljöteknologi,Institutioner vid LTH,Lunds Tekniska Högskola,Division of Building Services,Department of Building and Environmental Technology,Departments at LTH,Faculty of Engineering, LTH
-
- Wahlström, Åsa (författare)
- Lund University,Lunds universitet,Avdelningen för Installations- och klimatiseringslära,Institutionen för bygg- och miljöteknologi,Institutioner vid LTH,Lunds Tekniska Högskola,Division of Building Services,Department of Building and Environmental Technology,Departments at LTH,Faculty of Engineering, LTH,CIT Energy Management AB
-
visa fler...
-
- Fransson, Victor (författare)
- Lund University,Lunds universitet,Avdelningen för Installations- och klimatiseringslära,Institutionen för bygg- och miljöteknologi,Institutioner vid LTH,Lunds Tekniska Högskola,Division of Building Services,Department of Building and Environmental Technology,Departments at LTH,Faculty of Engineering, LTH
-
visa färre...
-
(creator_code:org_t)
- 2020-09-09
- 2022
- Engelska.
-
Ingår i: International Journal of Ventilation. - : Informa UK Limited. - 1473-3315 .- 2044-4044. ; 21:1, s. 35-52
- Relaterad länk:
-
http://dx.doi.org/10... (free)
-
visa fler...
-
https://www.tandfonl...
-
https://lup.lub.lu.s...
-
https://doi.org/10.1...
-
visa färre...
Abstract
Ämnesord
Stäng
- A novel DCV-system controls the air-change rate for each apartment in multifamily buildings based on two indoor air parameters: 1) the moisture load (supply), and 2) volatile organic compounds. With a central fan, but decentralized control boxes placed outside each apartment, the system controls the air-change rate for each apartment. This paper’s main aim is to determine the potential of this DCV-system, through a case study, to: 1) achieve good IAQ, 2) handle the moisture loads appropriately, and 3) achieve good energy efficiency in multifamily buildings. Furthermore, the paper aims to assess the possibility to achieve good IAQ by validating the DCV-system’s VOC-controls through measurements of CO2 in apartments. Field measurements show that the system responds appropriately to apartment-specific loads, and that acceptable emission and moisture loads are achieved in most apartments in the case study. The impact that the system has on the energy use was assessed through calculations based on the field measurements. The calculations show that the DCV-system saves energy used for heating the supply-air by 86% in comparison to a mechanically balanced ventilation system without heat recovery, and 22% in comparison to the same system but with heat recovery.
Ämnesord
- TEKNIK OCH TEKNOLOGIER -- Samhällsbyggnadsteknik -- Husbyggnad (hsv//swe)
- ENGINEERING AND TECHNOLOGY -- Civil Engineering -- Building Technologies (hsv//eng)
Nyckelord
- Demand control
- energy
- indoor air quality
- moisture
- ventilation
- volatile organic compounds