Sökning: onr:"swepub:oai:lup.lub.lu.se:f73ead79-c518-47ea-912b-297821202177" >
A Study of Reproduc...
A Study of Reproducibility of a Full-Scale Multi-Room Compartment Fire Experiment
-
- Johansson, Nils (författare)
- Lund University,Lunds universitet,Avdelningen för Brandteknik,Institutionen för bygg- och miljöteknologi,Institutioner vid LTH,Lunds Tekniska Högskola,Division of Fire Safety Engineering,Department of Building and Environmental Technology,Departments at LTH,Faculty of Engineering, LTH
-
- Svensson, Stefan (författare)
- Lund University,Lunds universitet,Avdelningen för Brandteknik,Institutionen för bygg- och miljöteknologi,Institutioner vid LTH,Lunds Tekniska Högskola,Division of Fire Safety Engineering,Department of Building and Environmental Technology,Departments at LTH,Faculty of Engineering, LTH
-
- Van Hees, Patrick (författare)
- Lund University,Lunds universitet,Avdelningen för Brandteknik,Institutionen för bygg- och miljöteknologi,Institutioner vid LTH,Lunds Tekniska Högskola,Division of Fire Safety Engineering,Department of Building and Environmental Technology,Departments at LTH,Faculty of Engineering, LTH
-
(creator_code:org_t)
- 2014-05-06
- 2015
- Engelska.
-
Ingår i: Fire Technology. - : Springer Science and Business Media LLC. - 0015-2684 .- 1572-8099. ; 51:3, s. 645-665
- Relaterad länk:
-
http://dx.doi.org/10...
-
visa fler...
-
https://lup.lub.lu.s...
-
https://doi.org/10.1...
-
visa färre...
Abstract
Ämnesord
Stäng
- A study of 45 pool fire tests is presented in this paper. All tests have been conducted in the same experimental setup but with four different ventilation scenarios. The experimental setup consisted of a three-room compartment connected to a stairway. The tests have been conducted during a 6-year period under slightly different ambient conditions. The purpose of this paper is to study and quantify the reproducibility of these tests with the aim to illustrate the degree of variability that can be expected in this kind of experiment and how the variability is affected by different ventilation scenarios. The 95% confidence interval of the measured temperature rise in the tests covered ±7% to 35% around the mean, depending on place of measurement and studied scenario. The variation in the results is due to both the variation of different weather conditions and other unknown parameters. It has not been possible to statistically distinguish between these two sources of variation. The data set allows to estimate the effect of random variations in experiments of fire behavior and smoke movement across compartments. The fuel of the pool fires is well defined and the mass loss is known, which makes the data of use in validation of multi-room compartment fire models.
Ämnesord
- TEKNIK OCH TEKNOLOGIER -- Samhällsbyggnadsteknik -- Husbyggnad (hsv//swe)
- ENGINEERING AND TECHNOLOGY -- Civil Engineering -- Building Technologies (hsv//eng)
Nyckelord
- Compartment fires
- Reproducibility
- Fire dynamics
- Functional analysis
Publikations- och innehållstyp
- art (ämneskategori)
- ref (ämneskategori)
Hitta via bibliotek
Till lärosätets databas