Impact of turbine availability and wake effect on the application of dynamic thermal rating of wind farm export transformers

Li, Zhongtian (author)
KTH,Elektromagnetism och fusionsfysik,KTH Royal Inst Technol, Sch Elect Engn & Comp Sci, Dept Electromagnet Engn, Stockholm, Sweden.
Hilber, Patrik, 1975- (author)
KTH,Elektromagnetism och fusionsfysik,KTH Royal Inst Technol, Sch Elect Engn & Comp Sci, Dept Electromagnet Engn, Stockholm, Sweden.
Laneryd, Tor (author)
Hitachi Energy Research, Västerås, Sweden,Hitachi Energy Res, Västerås, Sweden.
show more...
Navarro Diaz, Gonzalo (author)
Uppsala universitet,Vindenergi
Ivanell, Stefan, 1974- (author)
Uppsala universitet,Vindenergi
show less...
 (creator_code:org_t)
Elsevier BV, 2024
2024
English.
In: Energy Reports. - : Elsevier BV. - 2352-4847. ; 11, s. 1399-1411
  • Journal article (peer-reviewed)
Abstract Subject headings
Close  
  • Dynamic thermal rating allows transformers to operate beyond the nameplate rating according to the actual weather and loading conditions. This paper proposes a methodology to improve the application of this technology in the design of new transformers or in the operation of existing transformers connected to wind farms by accurately predicting their load profiles, accounting for the influence of wake effect and turbine availability. Specifically, the variation of turbine availability due to the intermittent wind is considered in the load profile estimation. Additionally, a correction method, which can be incorporated into any wake model, is proposed to improve the accuracy of wake loss computation. A case study shows that the wake effect and the changing turbine availability shorten the time that the transformers maintain at full load, thereby reducing the aging rate of the wind farm export transformers. The findings suggest that considering these two factors in the DTR application can benefit the longevity and efficiency of wind farm exported transformers.

Subject headings

TEKNIK OCH TEKNOLOGIER  -- Maskinteknik -- Energiteknik (hsv//swe)
ENGINEERING AND TECHNOLOGY  -- Mechanical Engineering -- Energy Engineering (hsv//eng)
TEKNIK OCH TEKNOLOGIER  -- Elektroteknik och elektronik -- Annan elektroteknik och elektronik (hsv//swe)
ENGINEERING AND TECHNOLOGY  -- Electrical Engineering, Electronic Engineering, Information Engineering -- Other Electrical Engineering, Electronic Engineering, Information Engineering (hsv//eng)

Keyword

Transformer aging
Transformer loading
Turbine availability
Wake effect
Wind farm reliability

Publication and Content Type

ref (subject category)
art (subject category)

Find in a library

To the university's database

  • 1 of 1
  • Previous record
  • Next record
  •    To hitlist

Search outside SwePub

Kungliga biblioteket hanterar dina personuppgifter i enlighet med EU:s dataskyddsförordning (2018), GDPR. Läs mer om hur det funkar här.
Så här hanterar KB dina uppgifter vid användning av denna tjänst.

 
pil uppåt Close

Copy and save the link in order to return to this view