Test Method and Performance of Fire Detection Systems in Tunnels

Ingason, Haukur (author)
RISE,SP – Sveriges Tekniska Forskningsinstitut
Appel, Glenn (author)
Swedish Transport Administration, Sweden
Gehandler, Jonatan (author)
RISE,SP – Sveriges Tekniska Forskningsinstitut
show more...
Li, Ying Zhen (author)
RISE,SP – Sveriges Tekniska Forskningsinstitut
Nyman, Hans (author)
Brandskyddslaget AB, Sweden
Karlsson, Peter (author)
RISE,SP – Sveriges Tekniska Forskningsinstitut
Arvidson, Magnus (author)
RISE,SP – Sveriges Tekniska Forskningsinstitut
Lundström, Ulf (author)
Swedish Transport Administration, Sweden
Modig, Henric (author)
Swedish Transport Administration, Sweden
show less...
 (creator_code:org_t)
2016
2016
English.
In: Proceedings from the 7th International Symposium on Tunnel Safety and Security. ; , s. 485-496
  • Conference paper (other academic/artistic)
Abstract Subject headings
Close  
  • The results of a study carried out for the Swedish Transport Administration on fire detection in road tunnels is presented. Laboratory tests and numerous large-scale tests were carried out in order to verify a proposal for a test method for fire detection systems. The main aim was to investigate possible fire detector systems and to see if they could fulfil the requirement given by the Swedish Transport Administration to detect the fire within 90 seconds. The tests are presented as well as a recommendation for testing detection systems in Swedish road tunnels. In order to perform the fire test, pans of different sizes were tested in order to obtain a reasonable fire size. The method proposed requires the use of three 0.6 m diameter standard pans, each containing eight litres of 95 octane gasoline, and air flow velocities of 2 m/s and 6 m/s. It was found out that using only one 0.6 m pan is sufficient if early warning is required without identifying the position for the fire-fighting system.

Keyword

Fire detection
tunnel fire
test method
heat detection
smoke detection
flame detection

Publication and Content Type

vet (subject category)
kon (subject category)

To the university's database

  • 1 of 1
  • Previous record
  • Next record
  •    To hitlist

Search outside SwePub

Kungliga biblioteket hanterar dina personuppgifter i enlighet med EU:s dataskyddsförordning (2018), GDPR. Läs mer om hur det funkar här.
Så här hanterar KB dina uppgifter vid användning av denna tjänst.

 
pil uppåt Close

Copy and save the link in order to return to this view