Comparative analysis of optimal operation strategies for district heating and cooling system based on design and actual load

Deng, Na (author)
He, Guansong (author)
Gao, Yuan (author)
show more...
Yang, Bin (author)
Umeå universitet,Institutionen för tillämpad fysik och elektronik
Zhao, Jun (author)
He, Shunming (author)
Tian, Xue (author)
show less...
 (creator_code:org_t)
Elsevier BV, 2017
2017
English.
In: Applied Energy. - : Elsevier BV. - 0306-2619 .- 1872-9118. ; 205, s. 577-588
  • Journal article (peer-reviewed)
Abstract Subject headings
Close  
  • Computational load significantly influences energy and cost savings when developing an operation strategy for a district heating and cooling system. In this study, a model was identified to study the effects of the difference between design load and actual load on an optimal operation strategy. The established model is strongly dependent on the economy principle, and the proposed optimal strategy could achieve a dynamic balance between the users' load and the system energy supply. This model was validated at 30% load rate, which demonstrated an obvious cost saving of 63.6% under the actual load and 42.2% under the design load. Based on the current strategy, the optimal strategy at different load rates was analyzed with respect to two characteristics of each subsystem: energy outputs and operation costs. Furthermore, in the optimal strategy, changes in total operation costs and cost savings rates under different load rates are also discussed. The results showed that, when the load rate was changed from 30 to 75%, the savings rates based on the design load were 42.2, 17.9, 2.5, and 12.6%, and the savings rates based on the actual load were 63.6, 49.8, 34.3, and 25.7%, respectively. Based on the actual load, the energy savings advantage of the optimal operation strategy could be maximized, in particular, during the initial stage of project construction. Furthermore, the commercial software MATLAB was used for programming and calculations. The simulation results indicated that the application of the combined cooling, heating, and power system could significantly improve the cost-effectiveness.

Subject headings

TEKNIK OCH TEKNOLOGIER  -- Maskinteknik -- Energiteknik (hsv//swe)
ENGINEERING AND TECHNOLOGY  -- Mechanical Engineering -- Energy Engineering (hsv//eng)

Keyword

District heating and cooling
Design load
Actual load
Optimal operation strategy

Publication and Content Type

ref (subject category)
art (subject category)

Find in a library

To the university's database

  • 1 of 1
  • Previous record
  • Next record
  •    To hitlist

Find more in SwePub

By the author/editor
Deng, Na
He, Guansong
Gao, Yuan
Yang, Bin
Zhao, Jun
He, Shunming
show more...
Tian, Xue
show less...
About the subject
TEKNIK OCH TEKNOLOGIER
TEKNIK OCH TEKNO ...
and Maskinteknik
and Energiteknik
Articles in the publication
Applied Energy
By the university
Umeå University

Search outside SwePub

Kungliga biblioteket hanterar dina personuppgifter i enlighet med EU:s dataskyddsförordning (2018), GDPR. Läs mer om hur det funkar här.
Så här hanterar KB dina uppgifter vid användning av denna tjänst.

 
pil uppåt Close

Copy and save the link in order to return to this view