Vertical temperature gradients in apartments with hydronic radiator heating

Dahlblom, Mats (author)
Lund University,Lunds universitet,Avdelningen för Installations- och klimatiseringslära,Institutionen för bygg- och miljöteknologi,Institutioner vid LTH,Lunds Tekniska Högskola,Division of Building Services,Department of Building and Environmental Technology,Departments at LTH,Faculty of Engineering, LTH
Nordquist, Birgitta (author)
Lund University,Lunds universitet,Avdelningen för Installations- och klimatiseringslära,Institutionen för bygg- och miljöteknologi,Institutioner vid LTH,Lunds Tekniska Högskola,Division of Building Services,Department of Building and Environmental Technology,Departments at LTH,Faculty of Engineering, LTH
Wallentén, Petter (author)
Lund University,Lunds universitet,Avdelningen för Byggnadsfysik,Institutionen för bygg- och miljöteknologi,Institutioner vid LTH,Lunds Tekniska Högskola,Division of Building Physics,Department of Building and Environmental Technology,Departments at LTH,Faculty of Engineering, LTH
show more...
Harderup, Lars-Erik (author)
Lund University,Lunds universitet,Fuktcentrum,Annan verksamhet, LTH,Lunds Tekniska Högskola,Avdelningen för Byggnadsfysik,Institutionen för bygg- och miljöteknologi,Institutioner vid LTH,Moisture Research Centre,Other operations, LTH,Faculty of Engineering, LTH,Division of Building Physics,Department of Building and Environmental Technology,Departments at LTH,Faculty of Engineering, LTH
Jensen, Lars (author)
Lund University,Lunds universitet,Avdelningen för Installations- och klimatiseringslära,Institutionen för bygg- och miljöteknologi,Institutioner vid LTH,Lunds Tekniska Högskola,Division of Building Services,Department of Building and Environmental Technology,Departments at LTH,Faculty of Engineering, LTH
Johansson, Dennis (editor)
Bagge, Hans (editor)
Wahlström, Åsa (editor)
show less...
 (creator_code:org_t)
2018-12-12
2019
English 11 s.
In: Cold Climate HVAC 2018 : Sustainable Buildings in Cold Climates - Sustainable Buildings in Cold Climates. - Cham : Springer International Publishing. - 9783030006617 - 9783030006624 ; , s. 575-585
  • Conference paper (peer-reviewed)
Abstract Subject headings
Close  
  • A vertical temperature stratification normally exists in rooms during the heat-ing season in cold climates. An expression of the gradient in apartments heated by hydronic radiator heating systems with exhaust ventilation has ear-lier been developed assuming a dependency of the outdoor temperature. The expression was used by a public real estate owner when re-calculating meas-ured indoor temperature at 2.1 m above floor to 1.2 m above floor represent-ing the occupancy zone and used for individual metering and billing of space heating cost. To validate the suggested expression temperature measurements have been made at four heights in living rooms in apartments built in the 70’s. The heights includes 0.0, 0.1, 1.1 and 1.7 m above floor. The theoreti-cal expression has been compared to the full-scale measurements and in general the expression overestimates the vertical temperature gradient. The measured gradients are generally very low. The thermal comfort in the aspect of vertical temperature gradient is good for the studied period.
  • A vertical temperature stratification normally exists in rooms during the heat-ing season in cold climates. An expression of the gradient in apartments heated by hydronic radiator heating systems with exhaust ventilation has ear-lier been developed assuming a dependency of the outdoor temperature. The expression was used by a public real estate owner when re-calculating meas-ured indoor temperature at 2.1 m above floor to 1.2 m above floor represent-ing the occupancy zone and used for individual metering and billing of space heating cost. To validate the suggested expression temperature measurements have been made at four heights in living rooms in apartments built in the 70’s. The heights includes 0.0, 0.1, 1.1 and 1.7 m above floor. The theoreti-cal expression has been compared to the full-scale measurements and in general the expression overestimates the vertical temperature gradient. The measured gradients are generally very low. The thermal comfort in the aspect of vertical temperature gradient is good for the studied period.

Subject headings

TEKNIK OCH TEKNOLOGIER  -- Samhällsbyggnadsteknik -- Husbyggnad (hsv//swe)
ENGINEERING AND TECHNOLOGY  -- Civil Engineering -- Building Technologies (hsv//eng)

Publication and Content Type

kon (subject category)
ref (subject category)

Find in a library

To the university's database

  • 1 of 1
  • Previous record
  • Next record
  •    To hitlist

Search outside SwePub

Kungliga biblioteket hanterar dina personuppgifter i enlighet med EU:s dataskyddsförordning (2018), GDPR. Läs mer om hur det funkar här.
Så här hanterar KB dina uppgifter vid användning av denna tjänst.

 
pil uppåt Close

Copy and save the link in order to return to this view