Control methods for a direct-ground cooling system: An experimental study on office cooling with ground-coupled ceiling cooling panels

Arghand, Taha, 1982 (author)
Chalmers tekniska högskola,Chalmers University of Technology
Javed, Saqib, 1978 (author)
Chalmers tekniska högskola,Chalmers University of Technology
Trüschel, Anders, 1970 (author)
Chalmers tekniska högskola,Chalmers University of Technology
show more...
Dalenbäck, Jan-Olof, 1954 (author)
Chalmers tekniska högskola,Chalmers University of Technology
show less...
 (creator_code:org_t)
Elsevier BV, 2019
2019
English.
In: Energy and Buildings. - : Elsevier BV. - 0378-7788. ; 197, s. 47-56
  • Journal article (peer-reviewed)
Abstract Subject headings
Close  
  • This article experimentally investigates the performance of two control methods (the supply water temperature method and the water flow control method)for a direct-ground cooling system. The control methods were implemented through three types of indoor feedback controllers: 1)an on/off controller, 2)an on/off controller with a deadband and 3)P controller. The performances of the control methods were evaluated regarding room temperature stability and pump energy use. Ceiling cooling panels were employed to keep the test room air temperature at 25.0 °C under periodic heat gain conditions. The cooling system used a ground heat exchanger with a U-pipe in an 80-meter-deep borehole as a cooling source. The findings show that room air temperature was maintained close to the set-point with both control methods, but it was more stable with the temperature control method. In addition, condensation risk was easily preventable with the temperature control method. A parametric study showed that pump energy use when using two-position controllers could be as low as when using modulating controllers if the on-state flow rate of the circulating pump is selected in relation to the ground temperature and heat transfer characteristics of the heat exchanger.

Subject headings

TEKNIK OCH TEKNOLOGIER  -- Maskinteknik -- Energiteknik (hsv//swe)
ENGINEERING AND TECHNOLOGY  -- Mechanical Engineering -- Energy Engineering (hsv//eng)
TEKNIK OCH TEKNOLOGIER  -- Samhällsbyggnadsteknik -- Husbyggnad (hsv//swe)
ENGINEERING AND TECHNOLOGY  -- Civil Engineering -- Building Technologies (hsv//eng)
TEKNIK OCH TEKNOLOGIER  -- Elektroteknik och elektronik -- Reglerteknik (hsv//swe)
ENGINEERING AND TECHNOLOGY  -- Electrical Engineering, Electronic Engineering, Information Engineering -- Control Engineering (hsv//eng)

Keyword

Control methods
Energy performance
Controller
Radiant ceiling panel
High-temperature cooling
Direct-ground cooling

Publication and Content Type

art (subject category)
ref (subject category)

Find in a library

To the university's database

  • 1 of 1
  • Previous record
  • Next record
  •    To hitlist

Search outside SwePub

Kungliga biblioteket hanterar dina personuppgifter i enlighet med EU:s dataskyddsförordning (2018), GDPR. Läs mer om hur det funkar här.
Så här hanterar KB dina uppgifter vid användning av denna tjänst.

 
pil uppåt Close

Copy and save the link in order to return to this view