Mechanisms and performance of different fixed fire fighting systems in tunnels – summary of laboratory and tunnel fire tests

Li, Ying Zhen (författare)
RISE,Brand och Säkerhet
Ingason, Haukur (författare)
RISE,Brand och Säkerhet
Blom, Joel (författare)
RISE,Brand och Säkerhet
visa fler...
Arvidson, Magnus (författare)
RISE,Brand och Säkerhet
Försth, Michael (författare)
RISE,Brand och Säkerhet
visa färre...
 (creator_code:org_t)
ISBN 9789189896703
2024
Engelska 75 s.
  • Rapport (övrigt vetenskapligt/konstnärligt)
Abstract Ämnesord
Stäng  
  • This report presents both small scale laboratory tests and tunnel fire tests carried out in a FORMAS project. Four series of small scale laboratory tests were conducted to obtain the material properties, burning properties, water spray distributions, and spray droplet size distributions. The main efforts were, by adopting the Froude scaling, seven series of tests conducted in a about 50 m long container tunnel with a scale of 1 to 3. This report presents results on the influence of low pressure, medium pressure and high pressure water-based fixed fire fighting systems (FFFSs) on fire development, fire spread to adjacent vehicles, structural protection, tenability, smoke control, spray deflection and spray resistances. The focus is to compare the performance of three default FFFSs and to evaluate the efficiency of each of the FFFS. The results show that the default low pressure FFFS performs well in term of suppressing the fire development, preventing the fire spread to nearby vehicles, providing tenable conditions for evacuation and rescue service, protecting tunnel structure and easing the problem with spray deflection due to tunnel ventilation. The default high pressure FFFS is usually on the opposite side while the default medium pressure FFFS usually lie in between.

Ämnesord

TEKNIK OCH TEKNOLOGIER  -- Samhällsbyggnadsteknik (hsv//swe)
ENGINEERING AND TECHNOLOGY  -- Civil Engineering (hsv//eng)

Nyckelord

tunnel fire
fixed fire fighting system
fire suppression
fire spread
ventilation
smoke control
deflection
ventilation resistance
structural protection

Publikations- och innehållstyp

vet (ämneskategori)
rap (ämneskategori)

Hitta via bibliotek

Till lärosätets databas

Sök utanför SwePub

Kungliga biblioteket hanterar dina personuppgifter i enlighet med EU:s dataskyddsförordning (2018), GDPR. Läs mer om hur det funkar här.
Så här hanterar KB dina uppgifter vid användning av denna tjänst.

 
pil uppåt Stäng

Kopiera och spara länken för att återkomma till aktuell vy