Loss-Of-Excitation (LOE) condition of a generator may cause severe damages on both generator and the interconnected systems. This paper analyses the behaviours of different LOE protection schemes, such as R-X, G-B, P-Q and U-I schemes, for a hydro generator, which is connected to an infinite bus. Based on the simulation results, the reliability and stability of existing LOE protection schemes are compared and a preferred scheme is selected. An improvement to the scheme is also proposed to prevent the LOE relay incorrect operation during external faults, such as short-circuit faults on busbar or transmission lines.
Subject headings and genre
Added entries (persons, corporate bodies, meetings, titles ...)
-
Wang, J. P.
(author)
-
Gajic, Z.
(author)
-
Sao, C.
(author)
-
Ghandhari, MehrdadKTH,Elektriska energisystem(Swepub:kth)u14x6fsk
(author)
-
KTHElektriska energisystem
(creator_code:org_t)
Related titles
-
In:Developments in Power Systems Protection, 2012. DPSP 2012. 11th International Conference on: IET, s. 1-69781849196208
Internet link
Find in a library
To the university's database