Heat recovery and floating condensing in supermarkets

Arias, Jaime M. (författare)
KTH,Tillämpad termodynamik och kylteknik
Lundqvist, Per G. (författare)
KTH,Tillämpad termodynamik och kylteknik
 (creator_code:org_t)
Elsevier BV, 2006
2006
Engelska.
Ingår i: Energy and Buildings. - : Elsevier BV. - 0378-7788 .- 1872-6178. ; 38:2, s. 73-81
  • Tidskriftsartikel (refereegranskat)
Abstract Ämnesord
Stäng  
  • Supermarkets are great energy users in many countries. The potential for increased energy efficiency is large. One option is to utilize heat recovery (or heat reclaim) from condensers to heat the premises. Obviously this option is only interesting in relatively cold areas such as northern Europe, Canada, etc. An alternative to heat recovery is floating condensing pressure, which improves the coefficient of performance and decreases the energy consumption of the refrigeration system at lower outdoor temperature. Both heat recovery and floating condensing pressure can be utilized interchangeably depending on the heat requirements of the premises. A computer model that calculates the energy consumption in a supermarket with the possibility to simulate different system solutions for the refrigeration system has been developed at the Royal Institute of Technology, Department of Energy Technology. The software CyberMart is used in the present study to compare the potential of heat recovery and floating condensing in Swedish supermarkets. Measurements of different parameters such as temperatures, relative humidity and compressor power have been carried out in different supermarkets with heat recovery to validate the theoretical calculations. The present study shows that heating requirements can be covered completely by heat reclaim from the condenser. However, practical experiences show that installations are less efficient due to poor system solutions and/or control strategies. According to the results from CyberMart, the highest potential of energy saving is obtained from using a systems solution with both heat recovery and floating condensing.

Nyckelord

heat recovery
floating condensing
supermarkets
simulations
field measurements

Publikations- och innehållstyp

ref (ämneskategori)
art (ämneskategori)

Hitta via bibliotek

Till lärosätets databas

Hitta mer i SwePub

Av författaren/redakt...
Arias, Jaime M.
Lundqvist, Per G ...
Artiklar i publikationen
Energy and Build ...
Av lärosätet
Kungliga Tekniska Högskolan

Sök utanför SwePub

Kungliga biblioteket hanterar dina personuppgifter i enlighet med EU:s dataskyddsförordning (2018), GDPR. Läs mer om hur det funkar här.
Så här hanterar KB dina uppgifter vid användning av denna tjänst.

 
pil uppåt Stäng

Kopiera och spara länken för att återkomma till aktuell vy