Sökning: L773:9782955553909 >
Energetic and exerg...
Energetic and exergetic analysis of a low- Temperature based district heating substation for low energy buildings
-
- Castro Flores, José Fiacro (författare)
- KTH,Energiteknik
-
- Chiu, Justin Ningwei (författare)
- KTH,Energiteknik
-
Le Corre, O. (författare)
-
visa fler...
-
Lacarrière, B. (författare)
-
- Martin, Viktoria (författare)
- KTH,Energiteknik
-
visa färre...
-
(creator_code:org_t)
- International Conference on Efficiency, Cost, Optimization, Simulation and Environmental Impact of Energy Systems, 2015
- 2015
- Engelska.
-
Ingår i: ECOS 2015 - 28th International Conference on Efficiency, Cost, Optimization, Simulation and Environmental Impact of Energy Systems. - : International Conference on Efficiency, Cost, Optimization, Simulation and Environmental Impact of Energy Systems. - 9782955553909
- Relaterad länk:
-
https://urn.kb.se/re...
Abstract
Ämnesord
Stäng
- District Heating (DH) technology contributes to the low GHG emissions energy system, facilitates a renewable energy usage, and increases the overall system efficiency, while providing the necessary heating services to the built environment. However, the existing DH technology may not be technically and economically effective to service buildings with low-energy demands. Here, low- Temperature based district heating (LTDH) provides a better match between supply and demand in terms of energy quality. This paper deals with the energy and exergy analyses of a LTDH substation supplying a secondary LTDH network as a subnet of the existing DH system. The substation is supplied with a mix of supply and return flows from the main DH network. An energy and exergy analysis was employed based on modelling and simulation to compare the performance of two proposed substation configurations to that of a conventional DH substation operating at low- Temperature. The study was performed for a year round outdoor temperatures scenario under steady-state conditions. The exergy destruction at the system components was identified and compared. The results of this analysis show that by using the low- Temperature flow from the DH return pipe, the final exergy efficiency of the overall system is increased. On the other hand, assuming an adiabatic system the energy performance stays the same. As compared with the conventional DH network, the integration of the proposed LTDH substation reduced the share of energy demand covered by the main DH supply by 20-25% and improved the overall exergy efficiency from 79% to 85-87% depending on the substation configuration. Based on the results, the solution presented is seen as an effective approach to reduce the system's losses, and to increase the quality match between the low-energy heating demands and the supply.
Ämnesord
- TEKNIK OCH TEKNOLOGIER -- Maskinteknik -- Energiteknik (hsv//swe)
- ENGINEERING AND TECHNOLOGY -- Mechanical Engineering -- Energy Engineering (hsv//eng)
Nyckelord
- District heating
- Efficiency
- Exergy
- Low temperature
- Substation
- Temperature cascading
- Economic and social effects
- Economics
- Environmental impact
- Greenhouse gases
- Heating
- Temperature
- Energetic and exergetic analysis
- Energy and exergy analysis
- Low energy buildings
- Low temperatures
- Modelling and simulations
- Steady-state condition
- Substation configurations
- Energy efficiency
Publikations- och innehållstyp
- ref (ämneskategori)
- kon (ämneskategori)
Hitta via bibliotek
Till lärosätets databas