Mathematical Modeling and Performance Analysis of Seawater Heat Exchanger in Closed-Loop Seawater-Source Heat Pump System

Wu, Zhenjing (författare)
Tianjin Univ, Sch Environm Sci & Technol, Tianjin 300072, Peoples R China.
You, Shijun (författare)
Tianjin Univ, Sch Environm Sci & Technol, Tianjin 300072, Peoples R China.
Zhang, Huan (författare)
Tianjin Univ, Sch Environm Sci & Technol, Tianjin 300072, Peoples R China.
visa fler...
Fan, Man (författare)
Tianjin Univ, Sch Environm Sci & Technol, Tianjin 300072, Peoples R China.
Zheng, Wandong (författare)
Tianjin Univ, Sch Environm Sci & Technol, Tianjin 300072, Peoples R China.
Wang, Yaran (författare)
Tianjin Univ, Sch Environm Sci & Technol, Tianjin 300072, Peoples R China.
Zhang, Yang (författare)
KTH,Energiprocesser
visa färre...
Tianjin Univ, Sch Environm Sci & Technol, Tianjin 300072, Peoples R China Energiprocesser (creator_code:org_t)
ASCE-AMER SOC CIVIL ENGINEERS, 2019
2019
Engelska.
Ingår i: Journal of energy engineering. - : ASCE-AMER SOC CIVIL ENGINEERS. - 0733-9402 .- 1943-7897. ; 145:4
  • Tidskriftsartikel (refereegranskat)
Abstract Ämnesord
Stäng  
  • The seawater source heat pump (SWHP) utilizes low-grade energy from seawater to satisfy heating/cooling requirements of coastal buildings. Compared with the open-loop SWHP system, the closed-loop system is more stable and reliable when used in cold regions because the seawater heat exchanger can mitigate icing and corrosion problems. This study established mathematical modeling for the seawater heat exchanger, which was validated by the experimental results, to estimate the heat transfer performance. The thermal performance of the seawater heat exchanger under different operating conditions was predicted, and the effects of several key parameters on thermal resistance were analyzed. The results revealed that the pipe wall thermal resistance of the original heat exchanger was the most important factor limiting the heat transfer. Hence, a cost analysis of the heat exchangers with different pipe materials was conducted, and the steel pipe with anticorrosive coating was proven to be optimal in reducing pipe wall thermal resistance and economy. The findings are useful in designing and optimizing the seawater heat exchanger and promoting the application of ocean thermal energy.

Ämnesord

TEKNIK OCH TEKNOLOGIER  -- Maskinteknik -- Energiteknik (hsv//swe)
ENGINEERING AND TECHNOLOGY  -- Mechanical Engineering -- Energy Engineering (hsv//eng)

Nyckelord

Seawater heat exchanger
Heat transfer modeling
Thermal resistance
Economic analysis

Publikations- och innehållstyp

ref (ämneskategori)
art (ämneskategori)

Hitta via bibliotek

Till lärosätets databas

Sök utanför SwePub

Kungliga biblioteket hanterar dina personuppgifter i enlighet med EU:s dataskyddsförordning (2018), GDPR. Läs mer om hur det funkar här.
Så här hanterar KB dina uppgifter vid användning av denna tjänst.

 
pil uppåt Stäng

Kopiera och spara länken för att återkomma till aktuell vy