Current Reference Control Scheme of Voltage Source Converters to Ensure the Existence of Stable Equilibrium Points During Grid Fault

Wang, Zhihao (författare)
Shandong Univ, Sch Elect Engn, Key Lab Power Syst Intelligent Dispatch & Control, Minist Educ, Jinan 250061, Peoples R China.
Zhu, Guofang (författare)
Shandong Univ, Sch Elect Engn, Key Lab Power Syst Intelligent Dispatch & Control, Minist Educ, Jinan 250061, Peoples R China.
Wu, Heng (författare)
Aalborg Univ, AAU Energy, DK-9220 Aalborg, Denmark.
visa fler...
Gao, Xuesong (författare)
Shandong Univ, Sch Elect Engn, Key Lab Power Syst Intelligent Dispatch & Control, Minist Educ, Jinan 250061, Peoples R China.
Ding, Lei (författare)
Shandong Univ, Sch Elect Engn, Key Lab Power Syst Intelligent Dispatch & Control, Minist Educ, Jinan 250061, Peoples R China.
Wang, Xiongfei (författare)
KTH,Elkraftteknik
visa färre...
Shandong Univ, Sch Elect Engn, Key Lab Power Syst Intelligent Dispatch & Control, Minist Educ, Jinan 250061, Peoples R China Aalborg Univ, AAU Energy, DK-9220 Aalborg, Denmark. (creator_code:org_t)
Institute of Electrical and Electronics Engineers (IEEE), 2023
2023
Engelska.
Ingår i: IEEE transactions on power electronics. - : Institute of Electrical and Electronics Engineers (IEEE). - 0885-8993 .- 1941-0107. ; 38:9, s. 10750-10765
  • Tidskriftsartikel (refereegranskat)
Abstract Ämnesord
Stäng  
  • Maintaining synchronization with the grid during fault ride-through (FRT) is essential for grid-connected voltage source converters (VSCs). However, improper current references can lead to a loss of synchronization during FRT due to the nonexistence of stable equilibrium points (SEPs). While the mechanism of SEPs has been explained, the development of control schemes ensuring their existence remains challenging due to the difficulty of obtaining real-time grid parameters during FRT. To address this issue, this article proposes a novel current reference control scheme that only requires prefault grid parameters. By analyzing the changes in grid parameters caused by faults and characterizing the correspondence between the during-fault and prefault grid parameters, a voltage-dependent current reference control scheme is proposed. Since no real-time grid parameter estimation is needed during FRT, the proposed control scheme is practical and easy to implement. Simulation studies using DIgSILENT PowerFactory demonstrate that the proposed control scheme enables the VSC to maintain synchronization with the grid under the conditions of short-circuit ratio equaling 1.3 and grid voltage dropping to 0.1 p.u. Moreover, experiments further verify the effectiveness and feasibility of the proposed control scheme.

Ämnesord

TEKNIK OCH TEKNOLOGIER  -- Elektroteknik och elektronik -- Reglerteknik (hsv//swe)
ENGINEERING AND TECHNOLOGY  -- Electrical Engineering, Electronic Engineering, Information Engineering -- Control Engineering (hsv//eng)

Nyckelord

Fault ride-through (FRT)
loss of synchronization (LOS)
stable equilibrium point (SEP)
voltage source converter (VSC)

Publikations- och innehållstyp

ref (ämneskategori)
art (ämneskategori)

Hitta via bibliotek

Till lärosätets databas

Sök utanför SwePub

Kungliga biblioteket hanterar dina personuppgifter i enlighet med EU:s dataskyddsförordning (2018), GDPR. Läs mer om hur det funkar här.
Så här hanterar KB dina uppgifter vid användning av denna tjänst.

 
pil uppåt Stäng

Kopiera och spara länken för att återkomma till aktuell vy