Investigating the validity of existing definitions and empirical equations of effective length/area of grounding wire/grid for transient studies

Liu, Yaqing (author)
Uppsala universitet,Elektricitetslära och åskforskning
Theethayi, Nelson (author)
Uppsala universitet,Elektricitetslära och åskforskning,Elektricitetslära
Thottappillil, Rajeev, 1958- (author)
Uppsala universitet,Elektricitetslära och åskforskning,Elektricitetslära
 (creator_code:org_t)
Elsevier BV, 2007
2007
English.
In: Journal of Electrostatics. - : Elsevier BV. - 0304-3886 .- 1873-5738. ; 65:5-6, s. 329-335
  • Journal article (peer-reviewed)
Abstract Subject headings
Close  
  • There are various definitions for effective length/area of grounding wire/grid for lightning transients [A.S. Farag, T.C. Cheng, D. Penn, Grounding terminations of lightning protective systems, IEEE Trans. Dielectics, Elect. Insul 5(6) (1998) 869-877; B.R. Gupta, B. Thapar, Impulse impedance of grounding grid, IEEE Trans. Power Apparatus Syayem PAS-99(6) (1980) 2357-2362; Y. Liu, N. Theethayi, R. Thottappillil, An engineering model for transient analysis of grounding system under lightning strikes: non-uniform transmission line approach. IEEE Trans. Power Delivery 20 (2) (2005) 722-730; M.I. Lorentzou, N.D. Hatziargriou, Modelling of long grounding conductors using EMTP, in: IPST'99, International Conference on Power System Transients, Budapest, 20-24 June, 1999; L.D. Grcev, M. Heimbach, Frequency dependent and transient characteristics of substation grounding system, IEEE Trans. Power Delivery 12 (1997) 172-178.]. The present work investigates and discusses the validity of those existing definitions. Further, practical methods for estimating the effective length/area of different grounding structures are proposed for engineering applications. The calculations for effective length/area based on non-uniform transmission line approach (Liu et al., 2005) show that, for a single grounding wire, the empirical equation for effective length in Farag et al. (1998) is not valid when the injection current has very fast rise time. Also, the empirical equation for effective length of grid edge in Gupta and Thapar (1980) is not applicable for grids with large inner mesh size.

Keyword

lightning
grounding wire and grid
effective length and lightning transient
TECHNOLOGY

Publication and Content Type

ref (subject category)
art (subject category)

Find in a library

To the university's database

Search outside SwePub

Kungliga biblioteket hanterar dina personuppgifter i enlighet med EU:s dataskyddsförordning (2018), GDPR. Läs mer om hur det funkar här.
Så här hanterar KB dina uppgifter vid användning av denna tjänst.

 
pil uppåt Close

Copy and save the link in order to return to this view