Sökning: WFRF:(Jonsson Hans) >
Modelling of EMC Sc...
Modelling of EMC Screens for Radio Base Stations : Part 2: Evaluation of Turbulence Models
-
- Anton, Raul (författare)
- KTH,Tillämpad termodynamik och kylteknik
-
- Jonsson, Hans (författare)
- KTH,Tillämpad termodynamik och kylteknik
-
- Moshfegh, Bahram (författare)
- University of Gävle
-
(creator_code:org_t)
- IEEE Press, 2004
- 2004
- Engelska.
-
Ingår i: Proc. 9th InterSociety Conf. on Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm 2004), Las Vegas, NV, USA. - : IEEE Press. - 0780383575 ; , s. 471-478
- Relaterad länk:
-
https://urn.kb.se/re...
Abstract
Ämnesord
Stäng
- The objective of this paper is to investigate the performance of five well-known turbulence models and 2 wall treatments, in order to predict the details of the flow patterns through an EMC (ElectroMagnetic Compatibility) screen. The employed turbulence models are investigated in the present study is four different eddy-viscosity models; the standard k-ε model, the renormalization group (RNG) k-ε model, the realizable k-ε model and the k-ω model, as well as the Reynolds stress model, RSM. The commercial finite volume code Fluent 6.1 was used for simulation. A steady-state three-dimensional model, which serves as the most accurate representation of the model, was used in order to predict the details of the air flow paths and pressure field. The flow was assumed to be isothermal, turbulent and incompressible. The numerical predictions were validated experimentally by using wind tunnel measurements and smoke visualization. The performances of the turbulence models are discussed and the RSM results are compared with other two-equation turbulence models. The result shows that choosing the right turbulence model and wall treatment does not have a great influence on the prediction of pressure drop and the velocity field. The pressure field is over predicted about 15% and the velocity average deviation at several locations before and after the screen is less than 10%. Simulations using a hydraulic impedance surface, i.e. without a detail modeling of the EMC screen, show that the pressure field is also over predicted and great differences are observed in the velocity field.
Ämnesord
- TEKNIK OCH TEKNOLOGIER -- Maskinteknik -- Energiteknik (hsv//swe)
- ENGINEERING AND TECHNOLOGY -- Mechanical Engineering -- Energy Engineering (hsv//eng)
Nyckelord
- RNG
- RSM
- k-ε
- k-ω
- pressure drop
- perforated plate
- porosity
- EMC screen
- subrack
- velocity profile
- flow pattern
- hydraulic impedance
Publikations- och innehållstyp
- ref (ämneskategori)
- kon (ämneskategori)
Hitta via bibliotek
Till lärosätets databas