The Response Time of Different SprinklerGlass Bulbs in a Residential Room FireScenario

Arvidson, Magnus (författare)
RISE,Safety
 (creator_code:org_t)
2018-05-22
2018
Engelska.
Ingår i: Fire technology. - : Springer Science and Business Media LLC. - 0015-2684 .- 1572-8099. ; 54:5, s. 1265-1282
  • Tidskriftsartikel (refereegranskat)
Abstract Ämnesord
Stäng  
  • The response time of fire sprinklers is essential for their performance,especially in applications where life safety protection is desired. The earlier the sprin-kler activates, the smaller the size of the fire. Most commercial residential sprinklersare fitted with 3 mm, 68C glass bulbs. However, thinner sprinkler glass bulbs withlower operating temperatures are available. The aim of this study was to determinethe response time—and the corresponding heat release rate—of different glass bulbsin a residential room fire scenario. A series of tests were conducted inside a compart-ment measuring 3.66 m by 3.66 m having a ceiling height of 2.5 m. The compartmentwas either enclosed or had two walls removed to provide a more ventilated scenario.A propane gas burner was positioned at one of the corners. The mass flow rate ofthe gas was controlled such that either ‘slow’, ‘medium’ or ‘fast’ fire growth rate sce-narios were simulated. In each test, nine Response Time Index (RTI) and operatingtemperature combinations were tested. Each test was replicated three times. In addi-tion, two commercial fire detectors were tested. The results show that the fire is con-siderably smaller upon activation with a combination of a low RTI and a lowoperating temperature, as compared to the 3 mm, 68C glass bulb typically used forresidential sprinklers. The operating temperature proved to have a larger impact onthe results than the RTI. The heat from the fire was typically detected by the firedetectors prior to the activation of the sprinkler glass bulbs, especially for the ‘slow’and ‘medium’ fire growth rate scenarios.

Nyckelord

Sprinkler glass bulbs
Response Time Index (RTI)
Operating temperature
Fire detectors
Response time
Residential room fire scenario

Publikations- och innehållstyp

ref (ämneskategori)
art (ämneskategori)

Hitta via bibliotek

Till lärosätets databas

Hitta mer i SwePub

Av författaren/redakt...
Arvidson, Magnus
Artiklar i publikationen
Fire technology
Av lärosätet
RISE

Sök utanför SwePub

Kungliga biblioteket hanterar dina personuppgifter i enlighet med EU:s dataskyddsförordning (2018), GDPR. Läs mer om hur det funkar här.
Så här hanterar KB dina uppgifter vid användning av denna tjänst.

 
pil uppåt Stäng

Kopiera och spara länken för att återkomma till aktuell vy