Sökning: WFRF:(Olofsson Thomas 1968 ) >
The impact of contr...
The impact of control strategies on space heating system efficiency in low-energy buildings
-
- Brembilla, Christian, 1983- (författare)
- Umeå universitet,Institutionen för tillämpad fysik och elektronik,Energy Efficiency,Umeå University, Umeå, Sweden
-
- Renman, Ronny, 1990- (författare)
- Umeå universitet,Institutionen för tillämpad fysik och elektronik,Energy Efficiency,Umeå University, Umeå, Sweden
-
- Soleimani-Mohseni, Mohsen, 1968- (författare)
- Umeå universitet,Institutionen för tillämpad fysik och elektronik,Energy Efficiency,Umeå University, Umeå, Sweden
-
visa fler...
-
- Östin, Ronny (författare)
- Umeå universitet,Institutionen för tillämpad fysik och elektronik,Energy Efficiency,Umeå University, Umeå, Sweden
-
- Olofsson, Thomas, 1968- (författare)
- Umeå universitet,Institutionen för tillämpad fysik och elektronik,Umeå University, Umeå, Sweden
-
visa färre...
-
(creator_code:org_t)
- 2019-01-14
- 2019
- Engelska.
-
Ingår i: Building Services Engineering Research & Technology. - London : Sage Publications. - 0143-6244 .- 1477-0849. ; 40:6, s. 714-731
- Relaterad länk:
-
https://urn.kb.se/re...
-
visa fler...
-
https://doi.org/10.1...
-
https://urn.kb.se/re...
-
visa färre...
Abstract
Ämnesord
Stäng
- In this study efficiency factors measures the thermal energy performance for space heating. This study deals with the influence of control strategies on the effriciency factors of space heating and its distribution system. An adaptive control is developed and applied to two types of heating curves (linear and non-linear) for a low-energy building equipped with renewable energy sources. The building is modelled with a hybrid approach (law driven + data driven model). The design of the floor heating is calibrated and validated by assessing the uncertainty bands for low temperatures and mass flow rate. advantages and disavantages of linear and non-linear heating curves are highlighted to illustrate their impact on space heating thermodynamic behaviour and on the efficiency factors of the space heating system.Practical application: The study reveals that applying commercial building energy simulation software is worthwhile to determine reliable performance predictions. Oversimplified building models, in particular when considering building thermal mass, are not capable of simulating the thermodynamic response of a building subjected to different control strategies. The application of different heating cuirves (linear and non-linear) to massless building models leaves the amount of mass flow rate delivered to the space heating unchanged when the building is subjected to sharp variations of the outdoor temperature.
Ämnesord
- TEKNIK OCH TEKNOLOGIER -- Samhällsbyggnadsteknik -- Husbyggnad (hsv//swe)
- ENGINEERING AND TECHNOLOGY -- Civil Engineering -- Building Technologies (hsv//eng)
Nyckelord
- Efficiency factors of space heating and distribution system
- Calibration through uncertainty bands
- Hybrid model of low-energy building: law-driven + data-driven model
- Outdoor temperature compensation or heating curve
- Feedback and feed-forward control loop + adaptive control
- Solar radiation model
Publikations- och innehållstyp
- ref (ämneskategori)
- art (ämneskategori)
Hitta via bibliotek
Till lärosätets databas