Temperature measurements in a linear generator and marine substation for wave power

Boström, Cecilia (author)
Uppsala universitet,Elektricitetslära
Rahm, Magnus (author)
Uppsala universitet,Elektricitetslära
Svensson, Olle (author)
Uppsala universitet,Elektricitetslära
show more...
Strömstedt, Erland (author)
Uppsala universitet,Elektricitetslära
Savin, Andrej (author)
Uppsala universitet,Elektricitetslära
Waters, Rafael (author)
Uppsala universitet,Elektricitetslära
Leijon, Mats (author)
Uppsala universitet,Elektricitetslära
show less...
 (creator_code:org_t)
2010
2010
English.
In: PROCEEDINGS OF THE ASME 29TH INTERNATIONAL CONFERENCE ON OCEAN,   OFFSHORE AND ARCTIC ENGINEERING 2010, VOL 3. - 9780791849118 ; , s. 545-552
  • Conference paper (peer-reviewed)
Abstract Subject headings
Close  
  • This paper analyzes temperature measurements acquired in offshore operation of a wave energy converter array. The three directly driven wave energy converters have linear generators and are connected to a marine substation placed on the seabed. The highly irregular individual linear generator voltages are rectified and added on a common DC-link and inverted to 50 Hz to facilitate future grid-connection. The electrical power is transmitted to shore and converted to heat in a measuring station. First results of temperature measurements on substation components and on the stator of one of the linear generators are presented from operation in linear and in non-linear damping. Results indicate that there might be some convective heat transport in the substation vessel. If high power levels are extracted from the waves, this has to be considered when placing components in the substation vessel to avoid heating from neighbouring components. The results also indicate that the temperature increase in the linear generator stator is very small. Failure due to excessive heating of the stator winding PVC cable insulation is unlikely to occur even in very energetic sea states. Should this conclusion be incorrect, the thermal conductivity between the stator and the hull of the WEC could be enhanced. Another suggested alteration would be to lower the resistive losses by reducing the linear generator current density.

Keyword

TECHNOLOGY
TEKNIKVETENSKAP

Publication and Content Type

ref (subject category)
kon (subject category)