Sensor bias impact on efficient aeration control during diurnal load variations
-
- Samuelsson, Oscar (författare)
- Uppsala University,Uppsala universitet,Avdelningen för systemteknik,Reglerteknik,IVL Swedish Environm Res Inst, Stockholm, Sweden
-
- Olsson, Gustaf (författare)
- Lund University,Lunds universitet,Industriell elektroteknik och automation,Institutionen för biomedicinsk teknik,Institutioner vid LTH,Lunds Tekniska Högskola,Industrial Electrical Engineering and Automation,Department of Biomedical Engineering,Departments at LTH,Faculty of Engineering, LTH
-
- Lindblom, Erik (författare)
- Lund University,Lunds universitet,Industriell elektroteknik och automation,Institutionen för biomedicinsk teknik,Institutioner vid LTH,Lunds Tekniska Högskola,Industrial Electrical Engineering and Automation,Department of Biomedical Engineering,Departments at LTH,Faculty of Engineering, LTH
-
visa fler...
-
- Björk, Anders (författare)
- IVL Swedish Environm Res Inst, Stockholm, Sweden,IVL Swedish Environmental Research Institute
-
- Carlsson, Bengt (författare)
- Uppsala University,Uppsala universitet,Reglerteknik,Avdelningen för systemteknik
-
visa färre...
-
(creator_code:org_t)
- 2021-01-25
- 2021
- Engelska.
-
Ingår i: Water Science and Technology. - : IWA Publishing. - 0273-1223 .- 1996-9732. ; 83:6, s. 1335-1346
- Relaterad länk:
-
https://doi.org/10.2...
-
visa fler...
-
https://uu.diva-port... (primary) (Raw object)
-
https://iwaponline.c...
-
http://dx.doi.org/10... (free)
-
https://urn.kb.se/re...
-
https://doi.org/10.2...
-
https://lup.lub.lu.s...
-
visa färre...
Abstract
Ämnesord
Stäng
- This study highlights the need to increase our understand of the interplay between sensor drift and the performance of the automatic control system. The impact from biased sensors on the automatic control systems is rarely considered when different control strategies are assessed in water resource recovery facilities. Still, the harsh measurement environment with negative effects on sensor data quality is widely acknowledged. Simulations were used to show how sensor bias in an ammonium cascade feedback controller impact aeration energy efficiency and total nitrogen removal in an activated sludge process. Response surface methodology was used to reduce the required number of simulations, and to consider the combined effect of two simultaneously biased sensors. The effects from flow variations, negatively biased ammonium (-1 mg/L) and suspended solids sensors (-500 mg/L) reduced the nitrification aeration energy efficiency between 7 and 25 percent. Less impact was seen on total nitrogen removal. There were no added non-linear effects from two simultaneously biased sensors, apart from an interaction between a biased ammonium sensor and dissolved oxygen sensor located in the last aerated zone. Negative effects from sensor bias can partly be limited if the expected bias direction is considered when the controller setpoint-limits are defined.
Ämnesord
- TEKNIK OCH TEKNOLOGIER -- Samhällsbyggnadsteknik -- Vattenteknik (hsv//swe)
- ENGINEERING AND TECHNOLOGY -- Civil Engineering -- Water Engineering (hsv//eng)
- TEKNIK OCH TEKNOLOGIER -- Elektroteknik och elektronik -- Reglerteknik (hsv//swe)
- ENGINEERING AND TECHNOLOGY -- Electrical Engineering, Electronic Engineering, Information Engineering -- Control Engineering (hsv//eng)
Publikations- och innehållstyp
- ref (ämneskategori)
- art (ämneskategori)
Hitta via bibliotek
Till lärosätets databas