The impact of a DCV-system on the IAQ, energy use, and moisture safety in apartments - a case study

Abdul Hamid, Akram (författare)
Lund University,Lunds universitet,Avdelningen för Byggnadsfysik,Institutionen för bygg- och miljöteknologi,Institutioner vid LTH,Lunds Tekniska Högskola,Division of Building Physics,Department of Building and Environmental Technology,Departments at LTH,Faculty of Engineering, LTH
Johansson, Dennis (författare)
Lund University,Lunds universitet,Avdelningen för Installations- och klimatiseringslära,Institutionen för bygg- och miljöteknologi,Institutioner vid LTH,Lunds Tekniska Högskola,Division of Building Services,Department of Building and Environmental Technology,Departments at LTH,Faculty of Engineering, LTH
Wahlström, Åsa (författare)
Lund University,Lunds universitet,Avdelningen för Installations- och klimatiseringslära,Institutionen för bygg- och miljöteknologi,Institutioner vid LTH,Lunds Tekniska Högskola,Division of Building Services,Department of Building and Environmental Technology,Departments at LTH,Faculty of Engineering, LTH,CIT Energy Management AB
visa fler...
Fransson, Victor (författare)
Lund University,Lunds universitet,Avdelningen för Installations- och klimatiseringslära,Institutionen för bygg- och miljöteknologi,Institutioner vid LTH,Lunds Tekniska Högskola,Division of Building Services,Department of Building and Environmental Technology,Departments at LTH,Faculty of Engineering, LTH
visa färre...
 (creator_code:org_t)
2020-09-09
2022
Engelska.
Ingår i: International Journal of Ventilation. - : Informa UK Limited. - 1473-3315 .- 2044-4044. ; 21:1, s. 35-52
  • Tidskriftsartikel (refereegranskat)
Abstract Ämnesord
Stäng  
  • A novel DCV-system controls the air-change rate for each apartment in multifamily buildings based on two indoor air parameters: 1) the moisture load (supply), and 2) volatile organic compounds. With a central fan, but decentralized control boxes placed outside each apartment, the system controls the air-change rate for each apartment. This paper’s main aim is to determine the potential of this DCV-system, through a case study, to: 1) achieve good IAQ, 2) handle the moisture loads appropriately, and 3) achieve good energy efficiency in multifamily buildings. Furthermore, the paper aims to assess the possibility to achieve good IAQ by validating the DCV-system’s VOC-controls through measurements of CO2 in apartments. Field measurements show that the system responds appropriately to apartment-specific loads, and that acceptable emission and moisture loads are achieved in most apartments in the case study. The impact that the system has on the energy use was assessed through calculations based on the field measurements. The calculations show that the DCV-system saves energy used for heating the supply-air by 86% in comparison to a mechanically balanced ventilation system without heat recovery, and 22% in comparison to the same system but with heat recovery.

Ämnesord

TEKNIK OCH TEKNOLOGIER  -- Samhällsbyggnadsteknik -- Husbyggnad (hsv//swe)
ENGINEERING AND TECHNOLOGY  -- Civil Engineering -- Building Technologies (hsv//eng)

Nyckelord

Demand control
energy
indoor air quality
moisture
ventilation
volatile organic compounds

Publikations- och innehållstyp

art (ämneskategori)
ref (ämneskategori)

Hitta via bibliotek

Till lärosätets databas

Sök utanför SwePub

Kungliga biblioteket hanterar dina personuppgifter i enlighet med EU:s dataskyddsförordning (2018), GDPR. Läs mer om hur det funkar här.
Så här hanterar KB dina uppgifter vid användning av denna tjänst.

 
pil uppåt Stäng

Kopiera och spara länken för att återkomma till aktuell vy