Modeling and Experimental Verification of Grid Interaction of a DFIG Wind Turbine

Petersson, Andreas, 1974 (författare)
Chalmers tekniska högskola,Chalmers University of Technology
Thiringer, Torbjörn, 1966 (författare)
Chalmers tekniska högskola,Chalmers University of Technology
Harnefors, Lennart, 1968 (författare)
Mälardalens högskola,ABB
visa fler...
Petru, Tomas, 1974 (författare)
Chalmers tekniska högskola,Chalmers University of Technology
visa färre...
 (creator_code:org_t)
2005
2005
Engelska.
Ingår i: IEEE Transactions on Energy Conversion. - 1558-0059 .- 0885-8969. ; 20:4, s. 878- 886
  • Tidskriftsartikel (refereegranskat)
Abstract Ämnesord
Stäng  
  • The response of the doubly fed induction generator (DFIG) wind turbine system to grid disturbances is simulated and verified experimentally. The results are compared to the response that a fixed-speed wind turbine would have given. A voltage sag to 80% (80% remaining voltage) is handled very well, which is not the case for a fixed-speed wind turbine. A second-order model for prediction of the response of DFIG wind turbines is derived, and its simulated performance is successfully verified experimentally. The power quality impact by the DFIG wind turbine system is measured and evaluated. Steady-state impact, such as flicker emission, reactive power, and harmonic emission, is measured and analyzed. It is found that the flicker emission is very low, the reactive power is close to zero in the whole operating range, and the current THD is always lower than 5%.

Ämnesord

TEKNIK OCH TEKNOLOGIER  -- Elektroteknik och elektronik -- Annan elektroteknik och elektronik (hsv//swe)
ENGINEERING AND TECHNOLOGY  -- Electrical Engineering, Electronic Engineering, Information Engineering -- Other Electrical Engineering, Electronic Engineering, Information Engineering (hsv//eng)

Nyckelord

power quality
voltage sag
Doubly fed induction generator
wind turbine

Publikations- och innehållstyp

art (ämneskategori)
ref (ämneskategori)

Hitta via bibliotek

Till lärosätets databas

Sök utanför SwePub

Kungliga biblioteket hanterar dina personuppgifter i enlighet med EU:s dataskyddsförordning (2018), GDPR. Läs mer om hur det funkar här.
Så här hanterar KB dina uppgifter vid användning av denna tjänst.

 
pil uppåt Stäng

Kopiera och spara länken för att återkomma till aktuell vy