Extended field of application (EXAP) forreaction-to-fire Euro-classification of coppercommunication cables (CCC)
-
- Johansson, Richard (författare)
- RISE,SP Fire Research
-
- Post, Johan (författare)
- RISE,SP Fire Research
-
- Försth, Michael (författare)
- RISE,SP Fire Research
-
(creator_code:org_t)
- ISBN 9789188349552
- 2016
- Engelska 52 s.
-
Serie: SP Rapport, 0284-5172 ; 2016:53
- Relaterad länk:
-
https://ri.diva-port... (primary) (Raw object)
-
visa fler...
-
https://urn.kb.se/re...
-
visa färre...
Abstract
Ämnesord
Stäng
- The feasibility of an EXAP procedure for copper communication cables (CCC) has been investigated. The test set consisted of 47 different cables split into 9 families. An analysis method for quantifying the confidence of an EXAP procedure was defined.A similar EXAP procedure as for power cables was investigated, but where the safety margin sm was varied between 0% and 40% of the class limits for the corresponding Euroclasses. For power cables, and also for optical cables (OF) this safety margin was fixed to 10% of the class limits for the main classification (B2ca, Cca, and Dca) and 20% fire the smoke classes S1 and S2. For the analysed CCC it was found that the safety margin must be higher in order to obtain a confidence on the same level as for the OF EXAP already published in a Position Paper. The error rate for the OF EXAP was 2% for the main class. This error rate was obtained with a safety margin of 30% of the class limits for CCC. Even higher safety margins result in a lower error rate but a trade-off must be made between confidence in the EXAP and a reasonable, not too conservative, classification of CCC.Therefore a CCC EXAP is proposed with a safety margin sm = 30% of the class limits for the corresponding Euroclasses.Key words: EXAP, CPR, reaction to fire, copper communication cables, CCC
Publikations- och innehållstyp
- vet (ämneskategori)
- rap (ämneskategori)
Hitta via bibliotek
Till lärosätets databas