Airborne bacteria in hospital operating rooms during ongoing surgery

Alsved, Malin (författare)
Lund University,Lunds universitet,Ergonomi och aerosolteknologi,Institutionen för designvetenskaper,Institutioner vid LTH,Lunds Tekniska Högskola,Ergonomics and Aerosol Technology,Department of Design Sciences,Departments at LTH,Faculty of Engineering, LTH
Civilis, Anette (författare)
Helsingborg Hospital
Ekolind, Peter (författare)
Avidicare AB
visa fler...
Tammelin, Ann (författare)
Karolinska Institutet
Erichsen Andersson, Annette (författare)
University of Gothenburg
Jakobsson, Jonas (författare)
Lund University,Lunds universitet,Ergonomi och aerosolteknologi,Institutionen för designvetenskaper,Institutioner vid LTH,Lunds Tekniska Högskola,Ergonomics and Aerosol Technology,Department of Design Sciences,Departments at LTH,Faculty of Engineering, LTH
Svensson, Tobias (författare)
Ramstorp, Matts (författare)
No affiliation available (private)
Sadrizadeh, Sasan (författare)
KTH Royal Institute of Technology
Larsson, P A (författare)
Bohgard, Mats (författare)
Lund University,Lunds universitet,Metalund,Annan verksamhet, LTH,Lunds Tekniska Högskola,NanoLund: Centre for Nanoscience,Annan verksamhet, LTH,Ergonomi och aerosolteknologi,Institutionen för designvetenskaper,Institutioner vid LTH,Other operations, LTH,Faculty of Engineering, LTH,Other operations, LTH,Faculty of Engineering, LTH,Ergonomics and Aerosol Technology,Department of Design Sciences,Departments at LTH,Faculty of Engineering, LTH
Santl-Temkiv, Tina (författare)
Lund University,Lunds universitet,Ergonomi och aerosolteknologi,Institutionen för designvetenskaper,Institutioner vid LTH,Lunds Tekniska Högskola,Ergonomics and Aerosol Technology,Department of Design Sciences,Departments at LTH,Faculty of Engineering, LTH
Löndahl, Jakob (författare)
Lund University,Lunds universitet,Ergonomi och aerosolteknologi,Institutionen för designvetenskaper,Institutioner vid LTH,Lunds Tekniska Högskola,Ergonomics and Aerosol Technology,Department of Design Sciences,Departments at LTH,Faculty of Engineering, LTH
visa färre...
 (creator_code:org_t)
2018
2018
Engelska.
  • Konferensbidrag (refereegranskat)
Abstract Ämnesord
Stäng  
  • IntroductionPost-operative infections obtained from open-wound surgeries constitute an unnecessary load on both healthcare and affected patients. It is well established that increased air cleanliness reduces the number of post-operative infections. Therefore, the ventilation system is important in order to reduce the number of infectious particles in the air during surgery. Ventilation with high airflow, as in operating rooms, consumes a high amount of energy and it is thus desirable to find energy efficient solutions. ObjectivesThe purpose of this work was to evaluate air quality, energy efficiency and working environment comfort for three different ventilation techniques in operating rooms. MethodThe newly developed ventilation system temperature controlled airflow (TcAF) was compared with the conventionally used turbulent mixed airflow (TMA) and laminar airflow (LAF). In total, 750 air sample measurements were performed during 45 orthopaedic operations: 15 for each type of ventilation system [1]. The concentration of colony forming units (CFU)/m3 was measured at three locations in the rooms: close to the wound (<0.5 m), at the instrument table and peripherally in the room. The working environment comfort was evaluated in a questionnaire.ResultsOur study shows that both LAF and TcAF maintains CFU concentrations in the air during ongoing surgery significantly below 10 CFU/m3 at the wound and at the instrument table, and for TcAF also in the periphery of the room, see Figure 1. The median CFU concentration in TMA was at or above 10 CFU/m3 at all locations. TcAF used less than half the airflow to that of LAF, resulting in a 28% reduction in energy consumption. The working environment comfort was perceived less noisy and having less draft in the TcAF than the LAF ventilation.SummaryBoth the LAF and TcAF ventilation maintain high air cleanliness with low CFU concentrations throughout the operation. TMA is less efficient in removing bacteria from the air close to the patient.

Ämnesord

MEDICIN OCH HÄLSOVETENSKAP  -- Klinisk medicin -- Infektionsmedicin (hsv//swe)
MEDICAL AND HEALTH SCIENCES  -- Clinical Medicine -- Infectious Medicine (hsv//eng)