The impact of control strategies on space heating system efficiency in low-energy buildings

Brembilla, Christian, 1983- (författare)
Umeå universitet,Institutionen för tillämpad fysik och elektronik,Energy Efficiency,Umeå University, Umeå, Sweden
Renman, Ronny, 1990- (författare)
Umeå universitet,Institutionen för tillämpad fysik och elektronik,Energy Efficiency,Umeå University, Umeå, Sweden
Soleimani-Mohseni, Mohsen, 1968- (författare)
Umeå universitet,Institutionen för tillämpad fysik och elektronik,Energy Efficiency,Umeå University, Umeå, Sweden
visa fler...
Östin, Ronny (författare)
Umeå universitet,Institutionen för tillämpad fysik och elektronik,Energy Efficiency,Umeå University, Umeå, Sweden
Olofsson, Thomas, 1968- (författare)
Umeå universitet,Institutionen för tillämpad fysik och elektronik,Umeå University, Umeå, Sweden
visa färre...
 (creator_code:org_t)
2019-01-14
2019
Engelska.
Ingår i: Building Services Engineering Research & Technology. - London : Sage Publications. - 0143-6244 .- 1477-0849. ; 40:6, s. 714-731
  • Tidskriftsartikel (refereegranskat)
Abstract Ämnesord
Stäng  
  • In this study efficiency factors measures the thermal energy performance for space heating. This study deals with the influence of control strategies on the effriciency factors of space heating and its distribution system. An adaptive control is developed and applied to two types of heating curves (linear and non-linear) for a low-energy building equipped with renewable energy sources. The building is modelled with a hybrid approach (law driven + data driven model). The design of the floor heating is calibrated and validated by assessing the uncertainty bands for low temperatures and mass flow rate. advantages and disavantages of linear and non-linear heating curves are highlighted to illustrate their impact on space heating thermodynamic behaviour and on the efficiency factors of the space heating system.Practical application: The study reveals that applying commercial building energy simulation software  is worthwhile to determine reliable performance predictions. Oversimplified building models, in particular when considering building thermal mass, are not capable of simulating the thermodynamic response of a building subjected to different control strategies. The application of different heating cuirves (linear and non-linear) to massless building models leaves the amount of mass flow rate delivered to the space heating unchanged when the building is subjected to sharp variations of the outdoor temperature.

Ämnesord

TEKNIK OCH TEKNOLOGIER  -- Samhällsbyggnadsteknik -- Husbyggnad (hsv//swe)
ENGINEERING AND TECHNOLOGY  -- Civil Engineering -- Building Technologies (hsv//eng)

Nyckelord

Efficiency factors of space heating and distribution system
Calibration through uncertainty bands
Hybrid model of low-energy building: law-driven + data-driven model
Outdoor temperature compensation or heating curve
Feedback and feed-forward control loop + adaptive control
Solar radiation model

Publikations- och innehållstyp

ref (ämneskategori)
art (ämneskategori)

Hitta via bibliotek

Till lärosätets databas

Sök utanför SwePub

Kungliga biblioteket hanterar dina personuppgifter i enlighet med EU:s dataskyddsförordning (2018), GDPR. Läs mer om hur det funkar här.
Så här hanterar KB dina uppgifter vid användning av denna tjänst.

 
pil uppåt Stäng

Kopiera och spara länken för att återkomma till aktuell vy